§ 917 — SINGLE-STACK VENT SYSTEM
The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode P, § 917
Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/e166ccf8-0d1c-489c-a3da-0533046b2833
SECTION 917 SINGLE-STACK VENT SYSTEM
* * * P-917.6 Additional venting required. Additional venting shall be provided where more than one water closet discharges to a horizontal branch and where the distance from a fixture trap to the stack exceeds the limits in Section 917.4. Where additional venting is required, the fixture(s) shall be vented by individual vents, common vents, wet vents, circuit vents, or a combination waste and vent pipe. The dry vent extensions for the additional venting shall connect to a branch vent, vent stack, stack vent, air admittance valve, or shall terminate outdoors. * * *
Ask a question about Philadelphia law
Corpus searches the Philadelphia sections it holds and shows the ones that match, with their citations. Free, no sign-in.
