§ 33-19 — Construction and operation of cross-connection control program subject to approval of the Tennessee Department of Environment and Conservation under supervision of the Director

Code of Ordinances, City of Murfreesboro, Tennessee (Supp. No. 18: codified through Ordinance No. 26-O-38, enacted September 17, 2026) · Murfreesboro City Code § 33-19

Corpus is an independent public-information project, not the official City of Murfreesboro website. Stable reference: corpuslaw.us/code/67070df5-7780-48ce-8e38-a7b677567bbb

Section 33-19 - Construction and operation of cross-connection control program subject to approval of the Tennessee Department of Environment and Conservation under supervision of the Director.

(A) Compliance with T.C.A. The Department must comply with T.C.A. §§ 68-221-701 through 68-221-720, as well as the Tennessee Rules and Regulations for Public Water Systems which pertain to cross-connections, auxiliary intakes, bypasses, and interconnections, and establish an effective on-going program to control these undesirable water uses. (B) Regulated. (1) It shall be unlawful for any person to cause a cross-connection to be made; or allow one to exist for any purpose whatsoever unless the construction and operation of same have been approved by the Tennessee Department of Environment and Conservation, and the operation of such cross-connection, auxiliary intake, bypass or interconnection is at all times under the direction of the Director. (2) If, in the judgment of the Director, an approved backflow prevention assembly is required at the Department's water service connection to the Customer's premises, or at points within the premises, to protect the potable water supply, the Director shall compel the installation and maintenance of said assembly at the owner's expense. (3) For new installations, the Department shall inspect the site and/or review plans in order to determine the type of backflow prevention assembly, if any, that will be required, and notify the owners in writing of the required assembly. All required assemblies must be installed by owners and operable prior to initiation of water service. (4) For existing premises, the Department shall perform evaluations and inspections and shall require correction of violations in accordance with Murfreesboro City Code §§ 33-18 through 33-22. (C) Plumbing permit required. No installation, alteration or change shall be made of any backflow prevention assembly connected to the public water supply for water supply, fire protection, or any other purpose without first securing a suitable plumbing permit from the Building and Codes Department. A copy of such permit shall be displayed in a conspicuous place at the job site at all times from the time of issuance until the final inspection. (D) Surveys and Inspections. The Director shall survey and inspect all properties served by the public water supply where cross-connections with the public water supply are deemed possible. The frequency of surveys, inspections and reinspections are based on potential health hazards involved shall be established by the Director in accordance with guidelines acceptable to Tennessee Department of Environment and Conservation. The Director shall have the right to enter at any reasonable time any property served by a connection to the Department for the purpose of inspecting the piping system therein for cross-connections, auxiliary intakes, bypasses, or interconnections. On request, the owner, lessee, and occupant of any property so served shall furnish any pertinent information regarding the piping system on such property. The refusal of such information or refusal of access, when requested, shall be deemed evidence of the presence of cross-connections. (E) Correction of violations. (1) Any person found to have cross-connections, auxiliary intakes, bypasses, or interconnections in violation of the provisions of this article shall be allowed a reasonable time within which to comply with the provisions of this article. After a thorough investigation of existing conditions and an appraisal of time required for completing the work, the amount of time shall be designated by the Director, but in no case shall the time for correction exceed 90 days for high and low hazards and 14 business days for high risk hazards. (2) Where cross-connections, auxiliary intakes, bypasses, or interconnections are found that constitute an extreme hazard of immediate concern of contaminating the public water system, the Director shall require that immediate corrective action be taken to eliminate the threat to the public water system. When in the opinion of the Director an imminent threat to public health exists, the Director shall have the authority to terminate water service without prior notification. (3) Expeditious steps shall be taken to disconnect the public water system from the on-site piping system unless the imminent hazard is corrected immediately, subject to the right to a due process hearing upon timely request. The time allowed for preparation for a due process hearing shall be in relationship with the risk of hazard to the public; and may follow disconnection when the risk of public health and safety in the opinion of the Director warrant disconnection prior to a due process hearing. (4) The failure to correct conditions threatening the safety of the public water system prohibited by this article and T.C.A. § 68-221-711, within the time limits set by the Department, shall be grounds for denial of water service. If proper protection has not been provided after a reasonable time, the Director shall give the Customer legal notification that water service is to be discontinued, and physically separate the public water system from the Customer's on-site piping system in such a manner that the two systems cannot again be connected by an unauthorized person, subject to the right of a due process hearing upon timely request. The due process hearing may follow disconnection when the risk of public health and safety in the opinion of the Director warrant disconnection prior to a due process hearing. (F) Required protective device. (1) Where the nature of use of the water supplied to a premises by the water system is such that it is deemed: (a) Impractical to provide an effective air gap separation; (b) The owner and/or occupant of the premises cannot or is not willing to demonstrate to the Director that the water use and protective features of the plumbing are such as to pose no threat to the safety or potability of the water; (c) The nature and mode of operation within a premises are such that frequent alterations are made to the plumbing; (d) The nature of the premises is such that the use of the structure may change to a use wherein backflow prevention is required; (e) There is a likelihood that protective measures may be subverted, altered, or disconnected; or, (f) The plumbing from a private well enters the building served by the public water supply. The Director shall require the use of an approved protective assembly on the service line serving the premises to assure that any contamination that may originate in the Customer's premises is contained therein. (2) The protective assembly shall be of the type approved by the Tennessee Department of Environment and Conservation and the Director as to manufacture, model, size and application. The method of installation of backflow protective assemblies shall be approved by the Director prior to installation and shall comply with the criteria set forth by the Tennessee Department of Environment and Conservation and with the installation criteria set forth in subsection (G) below. The installation shall be at the expense of the owner or occupant of the premises. (3) Applications requiring backflow prevention assemblies include, but are not limited to, service and/or fire flow connections for most commercial and educational buildings, construction sites, all industrial, institutional, medical facilities, all fountains, lawn irrigation systems, swimming pools, softeners and other point of use treatment systems, and on all fire hydrant connections other than by the Fire Department in combating fires. (a) Class 1, Class 2, and Class 3 fire protection systems generally shall require a double check detector assembly, except a reduced pressure backflow prevention assembly shall be required where: [1] Underground fire sprinkler pipelines are parallel to and within ten feet horizontally of pipelines carrying sewage or significantly toxic wastes; [2] Premises have unusually complex piping systems; [3] Pumpers connecting to the system have corrosion inhibitors or other chemicals added to the tanks of the fire trucks. (b) Class 4, Class 5, and Class 6 fire protection systems shall require reduced pressure backflow prevention assemblies. (c) Wherever the fire sprinkler system piping is not an acceptable potable water system material, or chemicals such as liquid foam concentrates are used, a reduced pressure backflow prevention assembly shall be required. (4) Plumbing for commercial and educational buildings wherein backflow prevention assemblies are not immediately required shall be designed to accommodate such assemblies in conformance with standards for such assemblies, including the required drains. (5) Additionally, the Director may require internal and/or additional backflow prevention assemblies wherein it is deemed necessary to protect potable water supplies within the premises. (G) Installation Criteria. (1) Minimum acceptable criteria for the installation of reduced pressure zone type backflow prevention assemblies, and double check valve assemblies requiring regular inspection and testing shall include the following: (a) All required assemblies must be installed pursuant to Murfreesboro City Code § 23-2 by a person certified by the Tennessee Department of Environment and Conservation, Division of Drinking Water, or its successor. Evidence of current certification at the time of installation will be required. (b) All assemblies shall be installed in accordance with the manufacturer's installation instructions, and shall possess all test cocks and fittings required for testing the assembly. All fittings shall permit direct connection to Department test devices. (c) The entire assembly, including test cocks and valves, shall be easily accessible for testing and repair. (d) Reduced pressure backflow prevention assemblies shall be located a minimum of 12 inches plus the nominal diameter of the device above the floor surface. Maximum height above the floor surface shall not exceed 60 inches. (e) Clearance of assembly from wall surfaces or other obstructions shall be a minimum of six inches. (f) Assemblies shall be protected from freezing, vandalism, mechanical abuse, and from any corrosive, sticky, greasy, abrasive, or other damaging environment. (g) Assemblies shall be positioned where discharge from relief port will not create undesirable conditions. (h) An approved air-gap shall separate the relief port from any drainage system. (i) An approved strainer, fitted with a test cock, shall be installed immediately upstream of the backflow device or shut off valve before strainer. (j) Assemblies shall be located in an area free from submergence or flood potential. (k) A gravity drainage system is required on all installations. Generally, below ground installations will not be permitted. On certain slopes where installations below ground level may be permitted, a single or multiple gravity drain system may be used provided the single drain line is at least four times the area of the relief port or the multiple drain lines are at least two and one-half times the area. (l) Fire hydrant drains shall not be connected to the sewer, nor shall fire hydrants be installed in such a manner that backsiphonage/backflow through the drain may occur. (m) Where jockey (low volume-high pressure) pumps are utilized to maintain elevated pressure, as in a fire protection system, the discharge of the pump must be on the downstream side of any check valve or backflow prevention device. Where the supply for the jockey pump is taken from the upstream side or the check valve or backflow prevention assembly, an assembly of the same type as required on the main line shall be installed on the supply line. (n) High volume fire pumps shall be designed not to discharge below 20 psi in the Department's water mains. Ideally, such pumps should draw from an in-house reservoir fed by several supply lines. If any of the supply lines have a source other than the public water supply, all supply lines must have air gap discharges into the reservoir. (o) No backflow prevention assemblies or methods shall be installed in a place where they would create a safety hazard such as, but not limited to, over an electrical panel or above ceiling level. (p) All backflow prevention assemblies or methods shall be installed so that they are accessible for testing. (2) Where the use of water is critical to the continuance of normal operations or protection of life, property, or equipment, duplicate units shall be provided to avoid the necessity of discontinuing water service to test or repair the protective device. Where it is found that only one unit has been installed and the continuance of service is critical, the Director shall notify, in writing, the occupant of the premises of plans to interrupt water service and arrange for a mutually acceptable time to test or repair the assembly. In such cases, the Director may require the installation of a duplicate unit. The Director shall require the occupant of the premises to make all repairs indicated promptly, and to keep any protective assembly working properly. The expense of such repairs shall be borne by the owner or occupant of the premises. Repairs shall be made by qualified personnel, acceptable to the Director. The failure to maintain a backflow prevention assembly in proper working order shall be grounds for discontinuance of water service to a Customer's premises. Likewise the removal, bypassing, or altering of a protective assembly or the installation thereof so as to render an assembly ineffective shall constitute grounds for discontinuance of water service. Water service to such premises shall not be restored until the Customer has corrected or eliminated such conditions or defects to the satisfaction of the Director. (H) Testing of devices. (1) Assemblies shall be tested at least annually by a person possessing valid certification from the Tennessee Department of Environment and Conservation, Division of Drinking Water (or its successor) for the testing of such assemblies. (2) Records of all tests shall be provided to the Department. Personnel of the Department shall have the right to inspect and test the assemblies whenever deemed necessary by the Director. Water service shall not be disrupted to test the assembly without the prior knowledge of the occupant of the premises. (3) Testing of backflow prevention assemblies or methods shall be performed by the Department. The costs of testing shall be borne by the Customer. (4) Backflow prevention assemblies or methods shall be tested upon installation; when cleaned, repaired, or overhauled; when relocated; and, shall be tested and inspected at least once annually. (5) Backflow prevention assemblies or methods which are in place, but have been out of operation for more than three months, shall be tested before being put back into operation. Backflow prevention assemblies or methods used in seasonal applications shall be tested before being put into operation each season. (6) When water service has been terminated for non-compliance, the backflow prevention assembly or method shall be repaired or replaced prior to the resumption of water service. Backflow prevention assemblies or methods shall be retested by Department immediately after repair or replacement. (I) Nonpotable supplies. (1) The potable water system made available to premises served by the Department shall be protected from possible contamination as specified herein. Any water outlet which could be used for potable or domestic purposes and which is not supplied by the potable system must be labeled in a conspicuous manner as: WATER UNSAFE FOR DRINKING (2) The minimum acceptable sign shall have black letters at least 1 inch high located on a red background. (3) Color coding of pipelines in accordance with the American Society of Mechanical Engineers standard or the plumbing/building code adopted by the City of Murfreesboro may be required in locations where, in the judgment of the Director, such color coding is necessary to identify and protect the potable water supply. (J) Customer Duties. (1) The Customer shall be responsible for ensuring that no cross-connections exist without the approved backflow protection on the Customer's premises starting at the point of service from the public potable water system. (2) The Customer shall at the Customer's own expense cause installation, operation, and maintenance of the backflow prevention assemblies or methods on Customer's premises. (3) The Customer shall correct any malfunction of the backflow prevention assembly or method which is revealed by periodic testing. (4) The Customer shall inform the Department of any proposed or modified cross-connection and also any existing cross-connection of which the Customer is aware but has not been found by the Department. (5) The Customer should notify the Department, in writing, of backflow prevention assemblies or methods that are in place but have been out of operation for more than three months or have been removed for storage and reinstalled in order for the Department to test the assemblies before being put back into operation. (6) The Customer shall notify the Department of backflow prevention assemblies or devices used in seasonal applications and allow the Department to test the assemblies or devices before being put into operation each season. (7) The Customer shall not install a bypass around any backflow prevention assembly or method unless there is a backflow prevention assembly or method of the same type on the bypass. Customers who cannot shut down operation for testing of the assembly(ies) or method(s) must supply additional assemblies or methods necessary to allow testing to take place. (8) The Customer shall, within five business days after repairs are completed, provide the Department with copies of records of the installation and of all tests and repairs made to the backflow prevention assembly on a form provided by the Department. (9) In the event of a backflow incident, the Customer shall immediately notify the Department of the incident and take steps to confine the contamination or pollution. Water service will not be restored until corrective action is taken and approved after inspection by the Department. (10) The Customer shall maintain records of installations, repairs, overhauls, or replacements of backflow prevention assemblies or methods for at least five years and, upon request, such records shall be made available to the Department. (11) The Customer shall be responsible for the payment of all fees for permits, annual or semi-annual assembly or method testing, retesting in the case that the assembly or method fails to operate correctly, and reinspections for noncompliance with the Department's requirements. (K) Customer Non-compliance. The water service, both potable and repurified, may be discontinued in the case of non-compliance with this ordinance. Non-compliance includes, but is not limited to, the following: (1) Refusal to allow the Department access to the property to inspect for cross-connection(s). (2) Removal of a backflow prevention assembly or method that is required by the Department. (3) Bypassing of a backflow prevention assembly or method that is required by the Department. (4) Providing inadequate backflow prevention when potential or actual cross-connections exist. (5) Failure to install a backflow prevention assembly or method that is required by the Department. (6) Failure to test and/or properly repair a backflow prevention assembly or method as required by the Department. (7) Failure to comply with the requirements of this ordinance. (L) Provision applicable. The requirements contained herein shall apply to all premises served by the Department whether located inside or outside the corporate limits and is hereby made a part of the conditions required to be met for the City to provide water services to any premises. This Cross-Connection Article shall be rigidly enforced since it is essential for the protection of the water distribution system against the entrance of contamination. Any person aggrieved by the action of the Director is entitled to a due process hearing upon timely request

(Ord. No. 93-O-43 § 1, 04-01-93; Ord. No. 08-O-23 § 3, 07-10-08; Ord. No. 09-O-23 §§ 3, 4, 06-18-09)