§ 6-1-14 - REFRIGERATION CHILLERS.
A person who owns or operates a centrifugal chiller that uses a refrigerant shall: (1) install leak monitoring equipment in the mechanical equipment room; (2) check the leak monitoring equipment at least once each month; (3) if the leak monitoring equipment registers a leak of 10.0 parts per million or more, repair the chiller within 30 days; and (4) if the chiller uses refrigerant R-11 and is not operated continuously, install and maintain a positive pressure device or a high efficiency purge device.
Source: 1992 Code Section 4-3-13; Ord. 031023-10; Ord. 031211-11.