§ 114.064 — Underground storage tank materials
Code of Ordinances of the City of Edinburg, Texas (Codified through Ordinance No. 2026-5214, enacted June 2, 2026 (Supp. No. 14)) · Edinburg Code of Ordinances § 114.064
Corpus is an independent public-information project, not the official City of Edinburg website. Stable reference: corpuslaw.us/code/076249ea-d8d7-48a9-93de-79588ae64364
Sec. 114.064 - Underground storage tank materials.
All underground motor fuel storage tanks installed within the limits of the city must be constructed of galvanized steel, basic open hearth steel, or wrought iron of a minimum gauge (U.S. Standard), and the material and construction of such underground motor fuel storage tanks is hereby prescribed and fixed upon a schedule of capacity of such tanks as follows: Capacity | Minimum Thickness of Material 1 to 560 gallons capacity | 14-gauge U.S. Standard 561 to 1,100 gallons capacity | 12-gauge U.S. Standard 1,101 to 4,000 gallons capacity | 7-gauge U.S. Standard 4,001 to 10,500 gallons capacity | ¼-inch U.S. Standard 10,501 to 20,000 gallons capacity | 5/16 -inch U.S. Standard 20,001 to 30,000 gallons capacity | ⅜-inch U.S. Standard Over 30,000 gallons capacity | To be determined by the Building Inspector
(`82 Code, § 10-74) (Ord. 150, passed 10-21-52)
Ask a question about Edinburg law
Corpus searches the Edinburg sections it holds and shows the ones that match, with their citations. Free, no sign-in.
