All underground motor fuel storage tanks installed within the limits of the city must be constructed of galvanized steel, basic open hearth steel, or wrought iron of a minimum gauge (U.S. Standard), and the material and construction of such underground motor fuel storage tanks is hereby prescribed and fixed upon a schedule of capacity of such tanks as follows: Capacity | Minimum Thickness of Material 1 to 560 gallons capacity | 14-gauge U.S. Standard 561 to 1,100 gallons capacity | 12-gauge U.S. Standard 1,101 to 4,000 gallons capacity | 7-gauge U.S. Standard 4,001 to 10,500 gallons capacity | ¼-inch U.S. Standard 10,501 to 20,000 gallons capacity | 5/16 -inch U.S. Standard 20,001 to 30,000 gallons capacity | ⅜-inch U.S. Standard Over 30,000 gallons capacity | To be determined by the Building Inspector

(`82 Code, § 10-74) (Ord. 150, passed 10-21-52)