Sec. 114.067 - Vent openings on underground tanks.
All underground motor fuel storage tanks must be provided with a permanently open vent. All such vent openings must be screened with 30 by 30 brass mesh or its equivalent, and must provide adequate area for allowing a proper flow of air or vapor during filling operation. All vent pipes must be provided with weatherproof hoods and terminated at a point at least 12 feet above the top of the fill pipe, and never within less than three feet, measured horizontally and vertically, from any window or other building opening, and never less than 18 inches above the eaves of a roof when the vent pipe is run up the side of a building. In no case shall vent pipes be smaller than one and one-half-inch galvanized iron pipe. Vent pipes shall be installed with fall sufficient to allow any liquid in such pipes to drain back into the storage tank.
(`82 Code, § 10-77) (Ord. 150, passed 10-21-52)