Sec. 12-11. - Firefighter air replenishment system.

The International Fire Code, 2015 edition, Appendix L, is hereby amended to add Section L101.2 Required Locations to read as follows: The following buildings shall be equipped with Firefighter Air Replenishment Systems in accordance with this appendix: (1) Any new building 5 stories or higher; (2) Any new, non-residential building which is 500,000 square feet or more in size.

(Ord. No. 10639-2019, § 3, 5-21-19)