§ 12-4 — Location of fire hydrants
Code of Ordinances, City of Grand Prairie, Texas (Supp. No. 117, Update 1: codified through Ordinance No. 1857-2026, adopted April 27, 2026) · Grand Prairie City Code § 12-4
Corpus is an independent public-information project, not the official City of Grand Prairie website. Stable reference: corpuslaw.us/code/f89e8619-59bb-4586-89c1-29ba2455d38b
Sec. 12-4. - Location of fire hydrants.
(a) [Criteria required prior to grant of building permit.] No person shall be granted a building permit from the city unless the following fire hydrant location criteria have been met: (1) Land use districts relating to single-family and two-family dwellings. Fire hydrants shall be located at a maximum spacing of eight hundred (800) feet as measured along the length of the roadway, and no part of any structure will be farther than five hundred (500) feet from the fire hydrant as measured by the route that a fire hose would be laid according to the fire chief or his designee. (2) Land use districts relating to multiple-family dwelling, retail, commercial, central business or industrial structures. Fire hydrants shall be located at a maximum spacing of three hundred (300) feet as measured along the length of the roadway, and no part of any structure will be farther than four hundred (400) feet from the fire hydrants as measured by the route that a fire hose is laid according to the fire chief or his designee. Exceptions: a. For Group R3 and Group U occupancies, the distance requirement shall be six hundred (600) feet. b. For building equipped with an approved automatic sprinkler system installed in accordance with the International Fire Code the distance requirement shall be six hundred (600) feet. (3) All fire hydrants located along public streets shall be located not more than six (6) feet from the curb and shall face the street. Fire hydrants located on private property shall be accessible to the fire department at all times. (4) Additional fire hydrants may be required by the fire chief or his designee if, in the best professional judgment of the fire chief or his designee, such additional fire hydrants are required. (5) Land use districts zoned for agricultural uses shall conform to the locational requirements set forth in subsection 12-4(a)(1); provided, however, that alternative water supply may be permitted in lieu of fire hydrant requirements when there are no water mains within six hundred (600) feet of the property. Alternative water supply will be: a. Residential fire sprinkler system; b. Stored water supply as prescribed by the fire chief. (b) Appeals. If the fire chief decides to refuse a building permit on the basis of a perceived violation of this section, or decides to refuse a claimed exemption under this section, any person aggrieved by such decision may appeal such decision to the fire board of appeals within ten (10) days from the date that such aggrieved person is made aware of the decision of the fire chief.
(Ord. No. 5458, § 2, 8-8-95; Ord. No. 10167-2016, § 2, 10-11-16)
Ask a question about Grand Prairie law
Corpus searches the Grand Prairie sections it holds and shows the ones that match, with their citations. Free, no sign-in.