Sec. 11-112. - Fire hydrants—Location.

(a) All residential zoned property and use. As property is developed, fire hydrants shall be located at a maximum spacing of six hundred (600) feet as measured along the length of the roadway(s) and no part of the structure shall be farther than five hundred (500) feet from the fire hydrant as measured by the route that a fire hose would be laid. (b) All nonresidential zoned property or use. As the property is developed, fire hydrants shall be located at a maximum spacing of three hundred (300) feet as measured along the length of the roadway(s) and no part of the structure shall be farther than five hundred (500) feet from the fire hydrant as measured by the route that a fire hose is laid.

(Code 1963, Ch. 6, art. 7, § 2 [Ord. No. 73-56, § 1, 12-20-73]; Ord. No. 02-25, § I, 5-28-02; Ord. No. 15-061, § II, 10-27-15)