Sec. 11-113. - Same—Restrictions.
(a) All required fire hydrants shall be of the national standard three-way breakaway type no less than five and one-fourth (5-1/4) inches in size and shall conform to the provisions of the latest A.W.W.A. specifications C-502 and shall be placed upon water mains of no less than six (6) inches in size. (b) Valves shall be placed on all fire hydrant leads. (c) Required fire hydrants shall be installed so the breakaway point will be no less than three (3) inches, and no greater than five (5) inches above the grade surface. (d) A spacing of no less than six (6) inches shall be provided between the bottom of the barrel of the large steamer connection and the grade surface. (e) No fire hydrant located more than one thousand eight hundred (1,800) feet on a six-inch dead-end water main shall be considered as a required fire hydrant in the enforcement of this article. (f) No fire hydrant on a six-inch looped water main exceeding three thousand five hundred (3,500) feet in length shall be considered as a required fire hydrant in the enforcement of this article. (g) Except when it is determined by the fire chief that the required maximum hour demand plus the needed fire flow demand will be met, fire hydrants shall be installed on a separate water main when required on private property. (h) Fire hydrants when located on public property shall be located a minimum of two (2) feet and a maximum of six (6) feet behind the curb line. (i) All required fire hydrants placed on private property shall be adequately protected by either curb stops or concrete posts or other methods as approved by the fire chief, such stops or posts to be the responsibility of the landowner on which the fire hydrant is placed. (j) All required fire hydrants shall be installed so that the steamer connection will face the fire lane or street. (k) Fire hydrants, when placed at intersections or access drives to parking lots, when practical shall be placed so that no part of the fire truck will block the intersection or parking lot access when connections to the fire hydrant are made. (l) Fire hydrants required by this article located on private property shall be accessible to the fire department at all times. (m) The fire chief may, for cause, increase the distance of fire hydrants within ten (10) percent of the footage given in section 11-112. (n) All required fire hydrants shall be approved by the fire marshal and installed by the contractor prior to any construction above the structure's foundation. The building official may issue foundation permits prior to the installation and approval of all required fire hydrants.
(Code 1963, Ch. 6, art. 7, § 3; Ord. No. 73-56, § 1, 12-20-73; Ord. No. 86-9, § 1, 2-11-86; Ord. No. 86-59, § 1, 8-26-86; Ord. No. 09-015, § I, 2-24-09)
Ask a question about Killeen law
Corpus searches the Killeen sections it holds and shows the ones that match, with their citations. Free, no sign-in.