Sec. 31-115.09. - Air gap separation.
Air gaps provide maximum protection from backflow hazards and should be utilized when possible at all locations where health hazardous substances are at risk of entering the potable utilities system. (a) An air gap separation shall be at least twice the diameter of the supply pipeline measured vertically above the top rim of the receiving vessel and in no case less than one (1) inch. If splashing is a problem, tubular screens may be attached, or the supply line may be cut at a forty-five-degree angle. The air gap distance is measured from the bottom of the angle. Hoses are not allowed. (b) Air gap separations shall not be altered in any way without prior approval from the utilities department and must be available for inspection at all reasonable times. (c) Side walls, ribs or similar obstructions do not affect air gaps when spaced from the inside edge of the spout opening a distance greater than three (3) times the diameter of the effective opening for a single, or a distance greater than four (4) times the effective opening for two (2) intersecting walls.
(Ord. No. 2025-O-103, 6-2-25)