§ 38-172 — Potable connection to boilers
Code of the City of Portsmouth, Virginia (Codified through Ordinance No. 2026-64, enacted June 23, 2026. (Supp. No. 66)) · Portsmouth City Code § 38-172
Corpus is an independent public-information project, not the official City of Portsmouth website. Stable reference: corpuslaw.us/code/4784820c-6e18-4740-8e8d-85e7127f2d44
Sec. 38-172. - Potable connection to boilers.
Potable water connections to boilers shall be made through an air gap or provided with an approved backflow preventer. Potable water bypass arrangements on boilers shall be protected by a backflow preventer. If continuous service is required, two backflow preventers of the same type may be installed in parallel. Systems containing chemicals shall be protected with an air gap or a reduced pressure principle backflow preventer.
(Code 1973, § 38-67.5; Code 1988, § 38-172; Ord. No. 1992-3, § 1, 1-14-1992; Ord. No. 1994-3, § 5, 1-11-1994)