§ 15.30.145 — Subsection 507.5.7—Added—Installation, Location, and Marking of Fire Hydrants

Code of Ordinances of the City of Kennewick, Washington (Codified through Ordinance No. 26-6253, enacted September 15, 2026 (Supp. No. 19)) · Kennewick Municipal Code § 15.30.145

Corpus is an independent public-information project, not the official City of Kennewick website. Stable reference: corpuslaw.us/code/04501b89-316d-4c90-8744-f538dfb60127

15.30.145: - Subsection 507.5.7—Added—Installation, Location, and Marking of Fire Hydrants.

(1) Hydrants shall be installed in accordance with IFC Appendix C. (2) Hydrants shall be installed at locations approved by the fire code official and the Public Works director or their designees. (3) Where cul-de-sacs are greater than 200 feet in length, hydrants shall be installed within 20 feet of the entrance of the cul-de-sac and just before the curb return of the turn-around area of the cul-de-sac. (4) Hydrants shall be installed, flushed, and fully in service prior to combustible building materials arriving on a construction site or as otherwise required. (5) Hydrants shall be supplied in accordance with the most recent edition of the City of Kennewick Engineering Standard Specifications and Details. (6) Hydrants shall be installed adjacent to fire apparatus access roads. Hydrants equipped with steamer ports shall have such ports facing the fire apparatus access road. (7) Hydrants shall be required on each side of major arterial streets, or as otherwise approved. (8) Hydrants shall at all times remain accessible and unobstructed by natural vegetation, structures, or other objects and shall remain clearly visible to a distance of not less than 50 feet in any direction of vehicular approach. (9) Hydrants shall at all times be provided with a clear operating space having a radius of not less than 36 inches measured from the center of the hydrant. (10) Privately owned hydrants shall be in operational condition at all times and be inspected, tested, and maintained in accordance with the most recently adopted version of National Fire Protection Association (NFPA) Standard 24. Reports of inspection, testing, and maintenance service are required to be submitted to the fire code official. (11) Hydrants that are damaged or out of service shall be marked in a manner acceptable to the fire code official. The fire code official shall be notified of hydrants placed out-of- service. (12) Hydrants shall be painted High Gloss Safety Yellow in accordance with City standards.

(Ord. 25-6080 Sec. 1, 2025)