§ 15.30.173 — Subsection 903.3.9—Added—Installation Requirements (Automatic Sprinkler Systems)

Code of Ordinances of the City of Kennewick, Washington (Codified through Ordinance No. 26-6253, enacted September 15, 2026 (Supp. No. 19)) · Kennewick Municipal Code § 15.30.173

Corpus is an independent public-information project, not the official City of Kennewick website. Stable reference: corpuslaw.us/code/a24d3ba9-3398-43b5-8cb2-42da9f641f8f

15.30.173: - Subsection 903.3.9—Added—Installation Requirements (Automatic Sprinkler Systems).

(1) New and modified fire sprinkler systems shall be provided with a minimum of one exterior wall or remote post indicator control valve installed in a location approved by the fire code official. (2) New and modified fire sprinkler systems shall be designed such that the activation of the system will activate interior emergency evacuation audibility installed in the building. The interior audibility shall utilize horn/strobe devices that comply with and are installed to the standards of the Americans with Disabilities Act (ADA), Washington State ADA standards, and the applicable provisions of the IFC.

(Ord. 25-6080 Sec. 1, 2025)