13.01.090 Amendments to the International Fire Code – Chapter 9, Fire Protection Systems.
The following local amendments to Chapter 9 of the International Fire Code, entitled “Fire Protection and Life Safety Systems,” including all amendments enacted by the state of Washington, are hereby adopted and incorporated into the International Fire Code as follows: A. Fire protection systems – Scope and application. Section 901 of the International Fire Code, entitled “General,” is amended by substituting subsection 901.1 with the following: Sec. 901.1. Scope and application. The provisions of this chapter shall apply to all occupancies and buildings, shall specify where fire protection systems are required, and shall apply to the design, installation, inspection, operation, testing, and maintenance of all fire protection systems; however, nothing contained in this chapter shall diminish or reduce the requirements of any duly adopted building codes, including state and local amendments, or other city ordinances, resolutions, or regulations. In the event of any conflict in requirements among these codes, ordinances, resolutions, or regulations, the more stringent provision shall apply. B. Fire protection systems – Fire watch for impaired fire protection systems. Section 901 of the International Fire Code, entitled “Fire protection systems,” is amended by adding the following new subsection 901.7.7. Sec. 901.7.7. Fire watch for impaired fire protection systems. In the event of the emergency responder communication system, fire alarm system, fire sprinkler system or any other required fire protection system; or an excessive number of preventable alarm activations, the fire code official is authorized to require the building owner or occupant to provide approved standby personnel until the system is restored, repaired, or replaced. C. Fire protection systems – General. Section 901 of the International Fire Code, entitled “General,” is amended by adding the following new subsection 901.11: Sec 901.11. Emergency contacts. It shall be the responsibility of the owner of any monitored fire protection system to provide and maintain a minimum of three emergency contacts that are capable of responding to the system location with their monitoring company. D. Fire protection systems – Definitions. Section 902 of the International Fire Code, entitled “Definitions,” is amended by adding the following to the list in subsection 902.1: PROBLEMATIC FIRE PROTECTION SYSTEM E. Automatic sprinkler systems – Where required. Section 903 of the International Fire Code, entitled “Automatic Sprinkler Systems,” is amended by substituting subsection 903.2 with the following: Sec. 903.2. Where required. Approved automatic fire sprinkler systems shall be installed as follows: 1. In all buildings without adequate fire flow. Exception: Miscellaneous Group U Occupancies. 2. All new buildings and structures regulated by the International Building Code requiring 2,000 gallons per minute or more fire flow, or with a gross floor area of 10,000 or more square feet (929 m2), or where this code provides a more restrictive floor/fire area requirement, and shall be provided in all locations or where described by this code. Exception: Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries, and standby engines, provided those spaces or areas are equipped throughout with an automatic smoke detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1 hour fire barriers constructed in accordance with Section 707 of the International Building Code or not less than 2 hour horizontal assemblies constructed in accordance with Section 712 of the International Building Code, or both. 3. Where this code requires the installation of an automatic sprinkler system to protect an occupancy within an otherwise non-sprinklered building, then automatic sprinkler protection will be required throughout the entire building. 4. When the required fire apparatus access roadway grade is 12 percent or greater. F. Automatic sprinkler systems – Speculative use warehouses. Section 903 of the International Fire Code, entitled “Automatic Sprinkler Systems,” is amended by adding the following new subsection 903.2.9.5: Sec. 903.2.9.5. Speculative use warehouses. Where the occupant, tenant, or use of the building or storage commodity has not been determined or it is otherwise a speculative use warehouse or building, the automatic sprinkler system shall be designed and installed to protect not less than Class IV non-encapsulated commodities on wood pallets, with no solid, slatted, or wire mesh shelving, and with aisles that are 8 feet or more in width and up to 20 feet in height. G. Automatic sprinkler systems – Installation requirements. Section 903 of the International Fire Code, entitled “Automatic Sprinkler Systems,” is amended by substituting subsection 903.3 with the following: Sec. 903.3. Installation Requirements. Automatic sprinkler systems shall be designed and installed in accordance with Sections 903.3.1 through 903.3.9. H. Automatic sprinkler systems – Check valve. Section 903 of the International Fire Code, entitled “Automatic Sprinkler Systems,” is amended by adding the following new subsection 903.3.9: Sec. 903.3.9. Check valve. All automatic sprinkler system risers shall be equipped with a check valve. I. Automatic sprinkler systems – Riser room access. Section 903 of the International Fire Code, entitled “Automatic Sprinkler Systems,” is amended by adding the following new subsection 903.7: Sec. 903.7. Riser room access. All risers shall be located in a dedicated room with an exterior door, and with lighting and heat for the room. J. Fire alarm and detection systems – General. Section 907 of the International Fire Code, entitled “Fire Alarm and Detection Systems,” is amended by substituting subsection 907.1.3 with the following: Sec. 907.1.3. Equipment. Systems and their components shall be listed and approved for the purpose for which they are installed. All new alarm systems shall be addressable. Each device shall have its own address and shall annunciate individual addresses at a UL Central Station. K. Fire alarm and detection systems – Initiating device identification. Section 907 of the International Fire Code, entitled “Fire Alarm and Detection Systems,” is amended by substituting subsection 907.6.3 with the following: Sec. 907.6.3 Initiating device identification. The fire alarm system shall identify the specific initiating device address, location, device type, floor level where applicable and status including indication of normal, alarm, trouble and supervisory status, as appropriate. Exception: Special initiating devices that do not support individual device identification. L. Fire alarm and detection systems – Latched alarms. Section 907 of the International Fire Code, entitled “Fire Alarm and Detection Systems,” is amended by adding the following new subsection 907.12: Sec. 907.12. Latched alarms. All signals shall be automatically “latched” at the fire alarm control unit until their operated devices are returned to normal condition, and the control unit is manually reset. M. Fire alarm and detection systems – Resetting. Section 907 of the International Fire Code, entitled “Fire Alarm and Detection Systems,” is amended by adding the following new subsection 907.13: Sec. 907.13. Resetting. All fire alarm control units shall be reset only by an approved person. Sec. 907.13.1. Reset code. The reset code for the fire alarm control unit or keypad shall be 1-2-3-4-5. The reset code shall not be changed without approval of the fire code official. N. Fire alarm and detection systems – Fire alarm control unit location. Section 907 of the International Fire Code, entitled “Fire Alarm and Detection Systems,” is amended by adding the following new subsection 907.14: Sec. 907.14. Fire alarm control unit location. All fire alarm control units shall be located in the riser room designed and installed in accordance with Section 903.7, or an approved location. O. Fire protection systems – Signs. Section 912 of the International Fire Code, entitled “Fire Department Connections,” is amended by substituting 912.5 with the following: Sec. 912.5. Signs. Fire department connections shall be clearly identified in an approved manner. All fire department connections shall have an approved sign attached below the Siamese clapper. The sign shall specify the type of water-based fire protection system, the structure, and the building areas served.
(Ord. No. 3691, § 1, 5-4-04; Ord. No. 3810, § 2, 9-5-06; Ord. No. 3840, § 1, 5-15-07; Ord. No. 3957, § 1, 5-18-10; Ord. No. 4082, § 1, 5-21-13; Ord. No. 4201, § 1, 5-17-16; Ord. No. 4313, § 3, 3-5-19; Ord. No. 4386, § 1, 12-8-20; Ord. No. 4462, § 1, 5-16-23. Formerly 13.01.080)
Ask a question about Kent law
Corpus searches the Kent sections it holds and shows the ones that match, with their citations. Free, no sign-in.