§ 13.01.120 — Amendments to the International Fire Code – Appendix B, Fire-Flow Requirements for Buildings

Kent City Code (current through Ordinance 4547, passed August 18, 2026) · Kent City Code § 13.01.120

Corpus is an independent public-information project, not the official City of Kent website. Stable reference: corpuslaw.us/code/3bf42401-72c6-4fd2-8399-ef019ca4b178

13.01.120 Amendments to the International Fire Code – Appendix B, Fire-Flow Requirements for Buildings.

The following local amendments to Appendix B to the International Fire Code, entitled “Fire-Flow Requirements for Buildings,” including all amendments enacted by the state of Washington, are hereby adopted and incorporated into the International Fire Code as follows: A. Modifications – Increases. Section B103 of the International Fire Code, entitled “Modifications,” is amended by substituting subsection B103.2 with the following: B103.2. Increases. The fire chief is authorized to increase the fire-flow requirements where exposures could be impacted by fire. An increase shall not be more than twice that required for the building under consideration. Exception: For one- and two-family residences when either of the following conditions apply: 1. The building and exposure are equipped with the 1-hour fire resistant rated exterior walls tested in accordance with ASTM E 119 or UL 263 with exposure on the exterior side and projections with 1-hour underside protection, fire blocking installed from the wall top plate to the underside of the roof sheathing and no gable vent openings. 2. The walls are a distance greater than 11' to the nearest exposure or lot line; or face an unbuildable lot, tract or buffer. The distance shall be measured at right angles from the face of the wall. B. Fire-flow requirements for buildings. Section B105 of the International Fire Code, entitled “Fire-Flow Requirements for Buildings,” is amended by substituting section B105 with the following: B105.1. One- and two-family dwellings. Fire-flow requirements for one- and two-family dwellings shall be in accordance with Sections B105.1.1 through B105.1.2. B105.1.1. Buildings less than 3,600 square feet. The minimum fire-flow and flow duration requirements for buildings less than 3,600 square feet shall be 1,000 gallons per minute for 1 hour. Exception: A reduction in required fire-flow of 50 percent, as approved, is allowed when the building is equipped with an approved automatic sprinkler system. B105.1.2. Buildings greater than 3,600 square feet or more. The minimum fire-flow and flow duration requirements for buildings that are 3,600 square feet or larger shall not be less than that specified in Table B105.1(2). Exception: A reduction of fire-flow and flow duration to 1,000 gallons per minute for 1 hour, as approved, is allowed when the building is equipped with the following: 1. An approved automatic sprinkler system. B105.2. Buildings other than one- and two-family dwellings. The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings shall be as specified in Table B105.1(2). Exception: A reduction in required fire-flow of 50 percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system. The resulting fire-flow shall not be less than 1,500 gallons per minute for the prescribed duration as specified in Table B105.1(2). B105.2.1. Tents and Membrane structures. No fire flow is required for tents and membrane structures. B105.2.2. Accessory residential Group U buildings. Accessory residential Group U buildings shall comply with the requirements of B105.1. B105.3. Water supply for buildings equipped with an automatic sprinkler system. For buildings equipped with an automatic sprinkler system, the water supply shall be capable of providing the greater of: 1. The automatic sprinkler system demand, including hose stream allowance. 2. The required fire flow. C. Fire-flow requirements for buildings. Section B105 of the International Fire Code, entitled “Fire-Flow Requirements for Buildings,” is amended by deleting the following tables from Section B105: Table B105.1(1). Required Fire-Flow for One- and two-family dwellings, Group R-3 and R-4 Buildings and Townhouses. Table B105.2. Required Fire-Flow for Buildings Other than One- and two-family dwellings, Group R-3 and R-4 Buildings and Townhouses. D. Section B105 of the International Fire Code is amended by adding new subsection B105.4 as follows: B105.4. Alternative Fire Flow Mitigation. For development projects, where it has been determined not feasible to extend the water main by the local water purveyor, the following alternative fire flow mitigations are approved for use in accordance with Sections B105.4.1 through B105.4.2 B105.4.1. One- and two-family dwellings. Fire flow will not be required for one- and two-family dwellings if all of the following mitigations are met; 1. The fire-flow calculation area is less than 3600 square feet 2. The construction type of the dwelling is Type VA 3. The dwelling is equipped with an automatic fire sprinkler system installed in accordance with Section 903.3.1.3 with a water supply of no less than 30 minutes 4. The dwelling has a fire separation distance of no less than 150 feet on all sides B105.4.2. Buildings other than one- and two-family dwellings. Fire flow will not be required for buildings other than one- and two-family dwellings if all of the following mitigations are met; 1. The fire-flow calculation area is less than 3600 square feet 2. The construction type of the building is not Type VB 3. The building is equipped with an automatic fire sprinkler system installed in accordance with Section 903.3.1.1 with a water supply of no less than 30 minutes 4. The building has a fire separation distance of no less than 150 feet on all sides

(Ord. No. 3810, § 3, 9-5-06; Ord. No. 3840, § 1, 5-15-07; Ord. No. 3957, § 1, 5-18-10; Ord. No. 4082, § 1, 5-21-13; Ord. No. 4201, § 1, 5-17-16; Ord. No. 4386, § 1, 12-8-20; Ord. No. 4462, § 1, 5-16-23. Formerly 13.01.110)

Ask a question about Kent law

Corpus searches the Kent sections it holds and shows the ones that match, with their citations. Free, no sign-in.