§ 7.02.390 — Inspection and testing procedures of approved backflow preventers
Kent City Code (current through Ordinance 4547, passed August 18, 2026) · Kent City Code § 7.02.390
Corpus is an independent public-information project, not the official City of Kent website. Stable reference: corpuslaw.us/code/0ceee271-da55-48ae-b9a1-3cfd87d2d6e4
7.02.390 Inspection and testing procedures of approved backflow preventers.
A. Approved backflow preventers shall be inspected and tested: 1. At the time of initial installation; 2. Annually after initial installation; 3. After the approved backflow preventer is repaired; 4. After the approved backflow preventer is moved, relocated, reinstalled or reinstated; 5. After the approved backflow preventer fails testing or inspection and the cause of the failure has been corrected; 6. After installation or replumbing of an air gap; 7. After a backflow incident; 8. More often if tests indicate repeated failures. B. The consumer shall have all required inspections and tests performed by a backflow assembly tester certified by the Washington State Department of Health. The results shall be delivered to the city on a form acceptable to the city. C. If any required inspection and/or test is not performed, or if the approved backflow preventer does not successfully pass the required tests, the city may initiate enforcement as set forth in KCC 7.02.410.
(Ord. No. 4288, § 2, 11-20-18)