§ 103-169 — General requirements for heating equipment
Municipal Code of the City of La Crosse, Wisconsin (Codified through Ordinance No. 5384, enacted August 13, 2026. (Supp. No. 43)) · La Crosse Municipal Code § 103-169
Corpus is an independent public-information project, not the official City of La Crosse website. Stable reference: corpuslaw.us/code/1aa92991-673b-47d6-a969-77260c7f8a52
Sec. 103-169. - General requirements for heating equipment.
(a) Installation. (1) All heating equipment shall be connected to a chimney or an approved vent with a positive draft, which approved vent shall be installed according to manufacturer's specifications. (2) Automatic equipment shall incorporate a high limit control to ensure safe operation. A thermostat on an automatic space heater shall be construed as a high limit control. (3) Combustion air shall be supplied where needed to ensure proper combustion. (4) Automatic steam heating equipment shall have a low-water safety cut-out control. (5) Fuel supply fittings shall be mechanically tight, so as not to create a fire hazard. (6) Vent connectors shall have clearance to combustibles on all sides of 18 inches for solid and liquid fuels, and of six inches for gaseous fuel, unless less clearance is approved by Underwriter's Laboratories, Inc., or other approved testing laboratory. (b) Maintenance. (1) Flue passages, flue connectors, breeching, smoke pipes, chimneys and vents shall be kept clean and shall not restrict the flow of combustion gases. (2) Heating equipment shall be so maintained as to be gastight. a. Fire pots, combustion chambers, heat exchangers, flue passages and connected parts that are cracked, broken or burned through shall be repaired or replaced. b. Gaskets, caulking, welds and joints shall be gastight and shall not allow products of combustion to escape. c. Flue connectors, breeching, and smoke pipes that are not gastight shall be repaired or replaced. (c) State Codes. The State Heating, Ventilating and Air Conditioning Code (Wis. Admin. Code ch. SPS 364), International Fuel Gas Code and Wis. Admin. Code ch. SPS 323 are hereby adopted by reference. (d) Permits required on all types of heating apparatus. (1) Prior to performing any work concerning, affecting, or relating to the installation, construction, remodeling, locating, relocating, moving, replacing, converting, repairing, or resetting of any heat producing appliance connected with space heating or air conditioning equipment; or any other matter governed by the provisions of this division; a permit therefor shall be obtained by a person, firm, partnership, corporation, association or a combination thereof, who is qualified under the provisions of this Code, and it shall be unlawful to proceed with such work unless a permit shall first have been obtained and the permit fee in the amount established by resolution paid. (2) The above permit fees shall be doubled when work is commenced before a permit is obtained. Other penalties provided by this Code may also be invoked. (3) In addition to the above permit fees, for all additions, alterations and services to existing buildings and structures, record fees are required as established by resolution. (4) Beginning January 1, 2010, and each January 1 thereafter, all fees under this subsection (h) shall automatically increase by the Consumer Price Index for All Urban Consumers (SPI-U) or as approved by the Common Council. (e) Wood and solid fuel burning equipment. (1) This division includes all heating units, stoves, furnaces, boilers, free-standing or used in tandem with other heating systems that use wood, coal, or other solids as fuel. (2) No person shall operate or permit the operation of any heating equipment until inspected and approved by the Fire Department - Division of Fire Prevention and Building Safety. (3) Installation clearances to combustibles. a. Unlisted radiant type space heaters. 1. Top: 36 inches. 2. Back: 36 inches. 3. Side: 36 inches. 4. Front: 36 inches. 5. Install only on noncombustible or protected floor. b. Unlisted circulating type heaters. 1. Top: 36 inches. 2. Back: 12 inches. 3. Side: 12 inches. 4. Front: 24 inches. 5. Install only on noncombustible or protected floor. c. Furnaces central and add-on types; boilers central and add-on types. 1. Top: 18 inches. 2. Back: 18 inches. 3. Side: 18 inches. 4. Front: 48 inches. 5. Install only on noncombustible or protected floor. d. Dual fuel furnaces. 1. Top: 18 inches. 2. Back: 18 inches. 3. Side: 18 inches. 4. Front: 48 inches. 5. Install only on noncombustible or protected floor. e. Ranges—Cooking stoves. 1. Top: 30 inches. 2. Back: 24 inches. 3. Firing side: 24 inches. 4. Opposite side: 18 inches. 5. Install only on noncombustible or protected floor. Note: The above clearances apply unless otherwise shown on listed appliances, or approved wall protection is used. (4) Mounting of unit. a. On noncombustible floor, unit must be mounted on a firm level base. b. On combustible floors, all units without legs shall be mounted on four-inch thick hollow concrete or tile blocks covered with 24 U.S. gauge sheet metal. Such protection shall extend not less than 18 inches around the perimeter of unit. Equivalent protection will be acceptable. c. Units with legs on combustible floors. All units that have 18 inches or more of open space under the base of the unit may be mounted on combustible floors, provided the floor is protected by a stove board extending 18 inches in front, and 12 inches to side and rear. d. Units with shorter legs may be mounted on combustible floors with approved protection. Note: Above clearances apply unless otherwise shown on listed appliances. (5) Type and size of chimney. The chimney shall be sized so that the cross-sectional area is not smaller than the cross section area of the flue collar of the equipment to be connected to it. All masonry chimneys shall be constructed in accordance with this chapter and factory-built all fuel chimneys bearing a listing by a nationally recognized testing laboratory will be considered as approved. (6) Chimney connector (stovepipes and vents). a. Vent connectors shall not be less than 24 gauge steel. b. Vent connectors shall have an internal cross sectional area not less than that of flue collar of the equipment. c. Vent connectors shall have a rise in the horizontal portion of not less than one-fourth inch to the running foot so that the connection at the chimney is higher than the end at the equipment. d. The smoke pipe shall be well supported and fastened together with screws or rivets. e. The smoke pipe shall have 18 inches clearance to combustibles. f. The smoke pipe shall have a cast iron damper to control the draft, subject to manufacturer's specifications. g. The smoke pipe shall be connected to the masonry chimney with a metal or burned fire-clay thimble that is cemented to the liner with a cement designed for that purpose. h. Smoke pipes that pass through combustible partitions must use a ventilated metal thimble. (7) Duel fuel equipment. Shall be installed as per manufacturer's specifications. (8) Supplemental heating unit connection to existing system. Shall be installed as per manufacturer's specifications. (f) Electric heat, heat pumps and air conditioners. (1) All heating and cooling appliances, equipment, devices, controls, materials hereafter installed shall be approved or certified by a nationally recognized testing agency and shall comply with applicable nationally recognized standards covering safe operation, substantial and durable construction and acceptable performance. (2) Equipment shall be installed, serviced, maintained and used in accordance with the conditions of the approval by such nationally recognized agency. (3) Drawings shall be supplied showing the location of electrical heating equipment. (4) Heat loss calculations shall be furnished to show how electrical heating equipment was sized. (5) Drawings shall be supplied showing locations of condensing equipment of air conditioners and heat pumps. (6) Exhaust fans shall be ducted to the outside air and shall not terminate in attic ventilation spaces.
(Code 1980, § 18.01; Ord. No. 4911, § I(attch.), 1-14-2016; Ord. No. 5119, § II, 11-14-2019; Ord. No. 5365, § III, 3-12-2026)
Ask a question about La Crosse law
Corpus searches the La Crosse sections it holds and shows the ones that match, with their citations. Free, no sign-in.