§ 103-200 — Gas burner installations, 400,000 BTU and smaller
Municipal Code of the City of La Crosse, Wisconsin (Codified through Ordinance No. 5384, enacted August 13, 2026. (Supp. No. 43)) · La Crosse Municipal Code § 103-200
Corpus is an independent public-information project, not the official City of La Crosse website. Stable reference: corpuslaw.us/code/dc7f8763-0b27-4163-85e4-10d1199605a1
Sec. 103-200. - Gas burner installations, 400,000 BTU and smaller.
(a) Definitions. The following words, terms and phrases, when used in this section, shall have the meanings ascribed to them in this section, except where the context clearly indicates a different meaning: Atmospheric burner means a device in which air, at atmospheric pressure, is injected into the burner by a jet of gas under pressure. Conversion burner means a gas burning unit designed to supply gaseous fuel to and properly burn same in the combustion chamber of a boiler, furnace or other device originally designed to burn another fuel. Gas burner means a device for the final conveyance of gas or a mixture of gas and air to the combustion zone of a steam or hot water boiler, furnace, or to any device or unit used in connection with a space heating system, and shall include conversion burners, gas designed heating units, power gas burners, atmospheric gas burners, and all gas burners other than those used in connection with a space heating system whose input capacity is 75,000 BTU per hour or more. Gas burner equipment means and includes gas burners as above defined, together with all fans, flue pipes, blowers, control devices, accessories connected to the burners, and piping involved in supplying the burner. Gas designed heating unit means any space heating unit designed for the exclusive use of gaseous fuel, including such auxiliary heaters as gas logs, gas fireplaces, radiant heaters, etc. Power gas burner means a device in which either gas or air or both are supplied at pressure exceeding, for gas the house line pressure, and for air the atmospheric pressure. (b) Compliance. The construction, arrangement, manner of installation, alteration and repair of all gas burners and gas burner equipment having an input capacity of 400,000 BTU per hour or less, shall conform to the following provisions: (1) Certificate of approval of gas burners. a. No person shall install any gas burner until such burner has been approved by the Fire Department - Division of Fire Prevention and Building Safety. Applications for approval of gas burners shall be filed with the Fire Department - Division of Fire Prevention and Building Safety accompanied by a filing fee of in the amount established by resolution, which application and fee may be for approval of each manufacturer's complete line of gas burners. Applications shall be made on forms prescribed by the Fire Department - Division of Fire Prevention and Building Safety. b. The approval by the Fire Department - Division of Fire Prevention and Building Safety of a gas burner shall be evidenced by a certificate of approval permitting its installation in the City. This certificate of approval shall remain in force until or unless the burner approved is so modified or altered as to no longer conform to the specifications on the basis of which such certificate of approval was originally issued. c. Whenever a gas burner is modified or altered from the basis upon which the certificate of approval was issued, approval of such modification or alteration shall be secured from the Fire Department - Division of Fire Prevention and Building Safety before any such modified or altered burner is installed. d. Gas burners for which approval is requested shall conform with the applicable requirements of National Fuel Gas Code, 2009 Edition of ANSI Z223.1-NFPA 54 and any amendments thereto Wis. Admin. Code ch. SPS 365, together with the requirements of this section. 1. The construction of heating elements shall be subject to the approval of the Fire Department - Division of Fire Prevention and Building Safety. 2. Combustion chambers and flue gas passageways shall be readily accessible for inspection and cleaning. 3. The gas supply line to the pilot or pilots shall be connected ahead of the main burner regulator and appliances shut-off valve and shall be provided with a separate cock. Pilot tubes shall be constructed in one piece of substantial material. The safety pilot actuating mechanism shall be so mounted as to preclude the possibility of slippage. The pilot shall be of such design that it will permit the gas valve to open only when a proven source of ignition exists. The flame that lights the burner ports shall light from the flame that heats the safety pilots without use of runner slotted connecting ports on any installation which does not make use of escapement gas, from a diaphragm shut-off valve, as a flare to assist in the lighting of the burner. Appliances having more than one combustion chamber shall be provided with individual safety pilots. The safety pilot actuating mechanism must be substantial and positive in its action. Design shall be such that mechanical or electrical failure will shut off main gas supply. 4. Drilled port or slotted port burners shall have adjustable primary air control. The orifice may be of either the fixed or adjustable type. If of the adjustable type, the reduction of the size of the orifice opening shall not be attained by obstructing the fixed orifice opening. 5. Burners shall be sized according to the BTU rating shown in the regularly published literature of the burner manufacturer and under no conditions shall the burner be altered to exceed the rated maximum BTU input. Before approval, the burner manufacturer shall furnish the Fire Department - Division of Fire Prevention and Building Safety with a certified copy of literature showing capacity of burners with maximum ratings at various pressures together with such other information as the Fire Department - Division of Fire Prevention and Building Safety may require. (2) Installation of used gas burners. It shall be unlawful to install any used gas burner and no permit shall be issued authorizing such installation until the licensed installer shall have first submitted with his application for permit a copy of the purchase order stating that a used burner is to be installed and bearing an acknowledgement by the purchaser that such is the case together with a statement by the licensed installer that said burner has been reconditioned and will comply in every way with ordinance requirements for new equipment as to operation, safety standards and adjustments. No used gas burner shall be installed unless it is of a type, make and model currently approved for installation in La Crosse as evidenced by a certificate of approval. (3) Type of gas. The requirements of this division shall apply to gas burners supplied with manufactured or natural gas from the general distribution system within the City. Burners and their installation where supplied with other types of gas, such as bottled or liquefied petroleum gas shall conform to the requirements of this division where applicable together with the requirements of the American Gas Association and the National Board of Fire Underwriters pertaining to the type of gas to be used. (4) Ventilation. Gas burners and gas burner equipment shall not be installed for operation in a room where the normal facilities for ventilation do not permit proper combustion of the gas, unless special provision is made for supplying sufficient air for complete combustion. Gas burners, gas burner equipment and space heaters will not be permitted in bedrooms, rooms used for sleeping purposes, bathrooms, or any confined space or area unless proper provisions are made for the supply of primary and secondary air and air for combustion from outside the building. Provisions shall also be made for proper venting to the outside. Method of securing air for combustion and the proper venting of the appliance shall be secured from the Fire Department - Division of Fire Prevention and Building Safety before work is started on any specific installation. (5) Conversion burners. a. The installation of conversion burners shall be made in conformance with American Standards Association requirements for Installation of Domestic Gas Conversion Burners, ASA - Z21.8 - 1958, sponsored by the American Gas Association, dated August 12, 1958 N.F.P.A. 54 (2009) and Wis. Admin. Code ch. SPS 365. b. Before a gas burner is installed in any existing boiler or furnace, all flues, fire pots, combustion chambers and connecting joints through which flue gases are conducted, shall be thoroughly cleaned, examined for leaks and draft conditions and made gastight as shown by a smoke bomb test or its equivalent. c. The chimney flue and flue pipe shall be examined and reconditioned if necessary so that they will freely conduct the flue gases to the outside air. Where flue pipes are rusted or burned out, they shall be replaced by new pipe. d. Where a conversion gas burner is installed and an oil burner is removed, it shall be mandatory that the fill pipes to the oil storage tank be removed and all openings to the storage tank blocked except the vent pipe. (6) Draft hoods. a. Each gas burning unit shall be equipped with a draft hood or its equivalent designed to ensure the ready escape of the products of combustion in the event of no draft, back draft, or stoppage beyond the appliance; prevent a back draft from entering the appliance; and neutralize the effects of stack action of the flue upon the operation of the appliance. b. The draft hood shall be placed in and made a part of the flue pipe from the unit or shall be in the unit itself. Such device shall have a free area equal to or greater than the cross sectional area of the flue pipe connected thereof subject to the approval of the Fire Department - Division of Fire Prevention and Building Safety. c. The draft hood shall be located at a point not lower than the top of the highest flue passage in the unit. d. Units of the revertible flue type shall have the draft hood at least one foot higher than the top of the highest flue passage. Proper provision shall be made subject to the approval of the Fire Department - Division of Fire Prevention and Building Safety, to prevent the accumulation of gas in any part thereof. Revertible flue type furnace shall have a one-inch bleeder cut through if trapped more than 12 inches. (7) Flue pipes. a. The internal cross section area of the flue pipe between the appliance and the chimney liner shall be such as to provide not less than one square inch of flue area per 7500 hourly BTU input. In no case shall this flue pipe be larger than the next integral inch diameter above the size given in the following table: Minimum Permissible Flue Sizes For Gas Burner Installations Input Rating BTU Per Hour | Area of Flue Outlet | Diameter of Flue Pipe (Inches) 94,50 | 12.6 | 4 147,00 | 19.6 | 5 212,00 | 28.3 | 6 288,75 | 38.5 | 7 377,25 | 50.3 | 8 477,00 | 63.6 | 9 Based on one square inch flue area per 7500 BTU per hour input Note: If flue pipe exceeds ten feet in length or contains more than two elbows, use next size larger pipe and draft hood. In cases where the outlet from the unit is larger than the above indicated size, an orifice plate may be inserted, or a section of the flue pipe restricted to the size indicated. In special cases with high chimneys or flues, the above schedule of areas may be modified subject to specific approval of the Fire Department - Division of Fire Prevention and Building Safety. b. The draft hood should ordinarily be located adjacent to the unit. In cases where it appears desirable to place the draft hood at a distance from the unit, the size of the restricted section may be modified according to the length and rise of the flue pipe. c. The proportional section at the flue outlet of the unit eliminates the necessity of using an adjustable damper in the flue pipe and such damper will not be permitted. d. Where dampers are an integral part of the boiler or furnace, they shall be removed or permanently secured in the wide open position, except such dampers the function of which is to alter the passage of flue gases through the units, which shall be locked in such position as not to interfere with the normal operation of the unit. e. Material used for flue pipe shall be such as to resist the corrosive action of flue gases. f. Flue pipe of existing systems shall be relocated where necessary and new flue pipe installations shall be so made as to avoid sharp turns or other construction features which would create excessive resistance to the flow of flue gases. Flue pipes shall slope upward to chimney. g. Flue pipe shall be tightly connected to the chimney liner, so as to prevent infiltration of cold air. h. No baffles shall be applied which will interfere with the proper combustion of the gas. i. Flue pipe shall be well supported to prevent sagging and shall not be installed closer than six inches to any combustible building materials unless flue pipe is covered with the incombustible insulation such that the surface temperature of the exterior surface thereof attain a temperature of not higher than 125 degrees Fahrenheit when the unit is under continuous operation. j. All room heating equipment shall be of vented type and properly vented to an effective flue. Room heaters shall have 100 percent shut-off. (8) Gas burners. a. Gas burners of all types shall consist of assembled and tested units and shall be accompanied by complete and comprehensive installation and operation instructions. The burner or burners shall be located according to the manufacturer's instructions and shall be so secured that they will not twist, slide or drop out of position. b. The burners shall be so installed as to be readily accessible for cleaning and inspection. c. The burner or burners shall be so installed that no part of the flame impinges on the heating surface so as to cause incomplete combustion. d. Air shutters shall be adjusted to produce a proper flame at the prevailing gas pressure. e. On all pre-mix power burners an approved type of check valve shall be installed in the gas supply line to prevent back flow of air into the gas line. (9) Air intake. a. Where secondary air is necessary, secondary air opening or openings shall be provided, of sufficient area to supply an adequate amount of air for complete combustion under the specified draft conditions and at the maximum rate of firing. b. Where an automatic secondary air control is provided, the construction shall be such that, in case the control fails in any way, either the gas will shut off or the secondary air door will remain open. c. The air intake of power burners shall be so located as to prevent the possibility of accidental closure. The gas and air supply shall be equipped with controls coordinated to prevent opening of the gas supply until the air supply if adequate for proper combustion and to shut off the gas supply in the event of failure of the air supply. (10) Pilots. a. Each gas burner shall be equipped with safety device arranged to prevent the flow of gas through the main burner unless the pilot flame is burning; to consist of a thermostatic pilot or other similar type of safety device. The operation of this device shall not depend upon the closing of an electric circuit to shut off the main gas supply. b. Pilot burners shall be rigidly supported in such a manner that their position relative to the main burner or burners will be fixed. c. Pilot burners or burners shall be so placed that they can be safely lighted and they shall be readily accessible or removable for cleaning. d. Pilot lines shall be connected to vertical main gas supply lines or to the side or top of horizontal lines ahead of all controls including pressure regulators and appliance shut-off (except room heaters) and shall be provided with a separate cock. e. Thermostatic safety pilots shall be so adjusted that main gas supply will be shut off within three minutes after pilot flame has been extinguished under continuous operating conditions. f. Pilot burners shall be so designed and positioned that the holding flame on the pilot burner will ignite the gas burner providing the lighting pilot does not function. (11) Main shut-off valve or cock. A Manually operated approved shut-off valve or cock shall be installed at each unit to shut off the entire gas supply to the unit, except the pilot, in cases of emergency. Such valve or cock shall be so located that it is readily accessible and shall clearly indicate the "on" and "off" positions, or directions of rotation to open or close. Where a clock is provided the operating handle shall be securely attached to the plug in such manner that it may not be readily removed. Shut-off cock shall be approximately five feet above floor and shall be outside the jacket, except room heaters. A combination safety shut-off, operating, regulating and pilot control which incorporates programmed safe lighting features may be used subject to the approval of the Fire Department - Division of Fire Prevention and Building Safety. (12) Electric control valves. Electric control valves shall be installed according to the instructions furnished by the manufacturer. All heating equipment shall be automatically controlled by thermostat except with respect to radiant heaters installed in fireplaces. (13) Electric wiring. All electrical connections shall be made in conformity with the provisions of the Electrical Code of the City. (14) Gas pressure regulators. A gas pressure regulator approved by A.G.A. and by the Fire Department - Division of Fire Prevention and Building Safety shall be installed on all gas burner installations. The gas pressure regulator vent shall be piped into the combustion chamber except when using a regulator that has a restricted orifice type vent and said regulator is located inside the casing of the heating unit. (15) Limiting devices. The boiler or furnace shall be equipped with safety devices arranged to limit high steam pressures or water temperatures, as well as high air temperatures in warm air furnaces, and all such devices shall be subject to the approval of Fire Department - Division of Fire Prevention and Building Safety. Each gas fired steam boiler shall be equipped with a low-water cut-off, approved by the Fire Department - Division of Fire Prevention and Building Safety. Safety devices operated electrically shall not depend upon the closing of a circuit to shut off the main gas supply. This requirement shall not be construed as prohibiting the use of electrical regulating devices, provided the required safety devices are also installed. Controls shall be so connected that maximum inherent safety provided by such controls will be attained. (16) Safety shut-off valves. Safety shut-off valves shall be tested to assure gas-tightness of the seat when in the closed position; the valve assembly shall be gastight in all positions. Packing glands shall be designed so that the valve will not be made inoperative by excessive tightening of the packing nut. Either the valve shall incorporate means for requiring a manual operation for re-opening of the valve after it has closed or the electrical circuit shall be so arranged as to require a manual operation to re-open the valve after it has been closed. In no case shall valves be able to be opened manually until safety pilots are lighted and circuit completed or low-water cut-off circuit has been completed. (17) Piping. a. Gas piping installed for serving conversion burners or gas designed heating units shall be sized for a total pressure drop not exceeding 0.3 inches water gauge from the meter to the burner for the total connected load. A separate pipe from the meter is to be preferred and in no case shall the service pipe be smaller than the size of equipment connection. b. All gas piping and fittings from the meter to the gas units shall be standard weight new wrought iron or steel. c. All piping shall be screwed, flared, flanged, compression fittings or welded. Such screwed joints shall be made up with a thread compound or dope applied to the male threads only; such compounds shall be resistant to the action of the gas or gas-air mixture. d. All piping shall be installed in a good workmanship manner with proper hangers or supports approximately every eight feet apart so that the proper alignment will be retained. No soldered or sweat joints or cast iron fittings shall be permitted. Weaving or crooked gas piping shall not be approved. e. Gas piping shall be of a size and so installed so as to provide a supply of gas sufficient to meet maximum demand without undue loss of pressure between the meter and the unit. All gas piping shall be installed so as to conform with American Gas Association standards. f. All piping shall be graded one-fourth inch per ten feet, from the meter. A drip shall be installed at all low points. All pipes or tubing shall be tested after installation and proved free from leaks at not less than normal operating pressures. Tests shall not be made with a flame. Air may be used for testing or by other approved methods. When units are moved the piping shall be capped. No piping shall be left open at any time. g. Alternate materials and methods of installation may be approved by Fire Department - Division of Fire Prevention and Building Safety upon submittal of plans, materials and inspection schedule prior to commencing with the installation. Alternate installation must conform to National Fuel Gas Code, NFPA 54, 2009 and Wis. Admin. Code ch. SPS 365. (18) Adequacy of draft. In the event conditions at the time of installation are such that the chimney or vertical flue has insufficient natural draft to properly carry away the products of combustion or is subject to down drafts, provisions shall be made by the installer to rectify existing conditions or provide mechanical means of maintaining constant updrafts during appliance operation. (19) Adjustment of burners. After the piping has been thoroughly purged, the pilot burner shall be lighted and adjusted and the burners put into operation in accordance with the manufacturer's instructions. (20) Pilot operation. a. Pilot flames shall effectively ignite the gas at the main burner or burners and shall be adequately protected from drafts. A device which, under normal chimney draft conditions, is at least equal in performance to the draft hood hereinbefore provided for, shall be interpreted as fulfilling the second part of this requirement as far as chimney drafts are concerned. b. Pilot flames shall not become extinguished when the main burner or burners are turned on or off in a normal manner, either manually or by automatic controls. c. Luminous flame pilots shall not show carbon deposits when adjusted according to the manufacturer's instructions. d. Where escapement pilots are used, their flames shall be freely ignited by the constant burning pilot. (21) Burner operation. a. The flames from each burner shall freely ignite the gas from adjacent burners when operating at the prevailing gas pressure or when the main control valve is regulated to deliver about one-third the full gas rate, except where additional pilots are provided. b. Burner flames shall not flash back upon immediate ignition, nor upon turning the gas cock until the gas rate to the burner is about one-third the full supply. c. Burner flames shall not flash back when the gas is turned on or off by an automatic control mechanism. d. Main burner flames shall ignite freely, from each constant burning pilot, when the main control valve is regulated to deliver about one-third the full gas rate or when pilot flame is reduced to minimum point at which it will actuate the safety thermostatic device. e. Burners shall be of such design that ignition from pilots or pilot will carry to all ports or burner heads protected by the pilot at inputs from one-third to maximum ratings. f. When ignition is made in a normal manner, the flames shall not flash outside the unit. g. Burners shall not expel gas through air openings in mixer faces when operating at the prevailing pressure. h. In making tests, care shall be exercised to prevent the accumulation of unburned gas in the unit or flues which might result in explosion or fire. (22) Performance. a. The concentration of carbon dioxide shall not exceed nine percent and the concentration of carbon monoxide shall not exceed 0.04 percent. The concentration of oxygen in the flue products shall in no case be less than four percent nor more than ten percent. The flue gas temperature, as taken on the unit side of the draft hood shall not exceed 480 degrees Fahrenheit above that of the air temperature surrounding the unit. b. Method of test, gas designed equipment. The rate of flow of the gas shall be adjusted to within plus or minus two percent of the required hourly BTU input rating at the manifold pressure specified by the manufacturer. When the prevailing pressure is less than the manifold pressure specified, the gas rate shall be adjusted at the prevailing pressure. The unit shall be allowed to operate until the stack temperature becomes stabilized, after which a sample of the flue products shall be taken at a point in the flue after the outlet of the unit but ahead of the draft hood, and analyzed for carbon dioxide, carbon monoxide and oxygen. c. Method of test, conversion burners. The rate of flow of gas shall be adjusted to within plus or minus five percent of 1.7 times the calculated hourly BTU heat loss of the buildings in which it is installed. The unit shall be allowed to operate until the stack temperature becomes stabilized, after which a sample of the flue products shall be taken at a point in the flue after the outlet of the unit but ahead of the draft hood, and analyzed for carbon dioxide, carbon monoxide and oxygen. d. The various controls of the unit shall be checked by both inspector and installer, to ensure their operation. e. Upon completion of the test of any newly installed gas burning equipment as hereinabove provided, the installer shall file with the Fire Department - Division of Fire Prevention and Building Safety in duplicate, complete records of such test. (23) Instructions to the customers. a. The customer shall be thoroughly instructed by the installer as to the proper and safe operation of the unit before it is placed in continuous service, and a printed set of instructions shall be left with the customer. b. In the absence of the customer, printed instructions, enclosed in an envelope labeled "Instructions to Customer" and attached to the main gas valve of the unit by the installer, shall be construed as having fulfilled the aforementioned requirement. c. A metallic plate, suitably etched or stamped, setting forth detailed instructions for the safe lighting and shutting off of the unit, shall be permanently attached to the unit in a prominent position near the lighting apertures. The size of the type used shall be not smaller than ten point and the working container thereon shall be subject to the approval of the Fire Department - Division of Fire Prevention and Building Safety. This plate shall also state make and model numbers of the burner and show the rate hourly gas BTU input.
(Code 1980, § 18.04(K); Ord. No. 4911, § I(attch.), 1-14-2016)
Ask a question about La Crosse law
Corpus searches the La Crosse sections it holds and shows the ones that match, with their citations. Free, no sign-in.