18-29-609.4 Vacuum breaker installation.
Vacuum breakers shall be installed a minimum of 6 inches (150 mm) above the flood level rim of the fixture or device in accordance with Sections 18-29-608 through 18-29-608.17.1.2. The flood level rim of hose connections shall be the maximum height at which any hose is utilized.