17.40.330 - Materials of construction.
A. General. All materials permitted by the 1985 Uniform Building Code, including their appropriate allowable stresses and those existing configurations of materials specified herein, may be utilized to meet the requirements of this part.
B. Existing Materials.
1. Unreinforced Masonry Walls. Unreinforced masonry walls analyzed in accordance with this part may provide vertical support for roof and floor construction and resistance to lateral loads.
a. All units of both bearing and nonbearing walls shall be laid with full shoved mortar joints; all head, bed and wall (collar) joints shall be solidly filled with mortar; and the bonding of adjacent wythes of multi-wythe walls shall be as follows:
b. The facing and backing shall be bonded so that not less than four percent of the wall surface of each face is composed of headers extending not less than four inches into the backing. The distance between adjacent full-length headers shall not exceed twenty-four inches either vertically or horizontally. In walls where a single header does not extend through the wall, headers from the opposite sides shall overlap at least four inches, or headers from opposite sides shall be covered with another header course overlapping the header below at least four inches.
c. Wythes of walls not bonded as described above shall be considered as veneer. The veneer wythe shall not be included in the effective thickness used to calculate the height-to-thickness ratio and the shear capacity of the wall.
d. Tension stresses due to seismic forces normal to the wall may be neglected if the wall does not exceed the height-to-thickness ratio set forth in Table No. 1 of Section 17.40.320 F.1.b. and the in-plane shear stresses due to seismic loads set forth in Table No. 2. If the wall height-to-thickness ratio exceeds the specified limit, the wall may be supported by vertical bracing members designed to satisfy the requirements of the 1985 Uniform Building Code. The deflection of such bracing members at design loads shall not exceed one-tenth of the wall thickness.
TABLE NO. 2
VALUES FOR EXISTING MATERIALS 1
1. Horizontal diaphragms
a. Roofs with straight sheathing with the roof covering applied directly to the sheathing. | 100 PLF for seismic shear.
b. Roofs with diagonal sheathing with the roof covering applied directly to the sheathing. | 400 PLF for seismic shear.
c. Floors with straight tongue and groove sheathing. | 150 PLF for seismic shear.
d. Floors with straight sheathing and finished wood flooring. | 300 PLF for seismic shear.
e. Floors with diagonal sheathing and finished wood flooring. | 450 PLF for seismic shear.
f. Floors or roofs with straight sheathing and plaster applied to the joists or rafters. 2 | Add 50 PLF to the allowable values in items 1a and 1c.
2. Shear walls
Wood stud walls with lath and plaster. | 100 PLF for side for seismic shear.
3. Plain concrete footings | f'c = 1500 psi unless otherwise shown by tests.
4. Douglas Fir wood | Same as 1985 UBC values for No. 1 Douglas Fir. 3
5. Reinforcing steel | f'c = 18,000 psi maximum. 3
6. Structural steel | f'c = 20,000 psi maximum. 3
1 Material must be sound and in good condition.
2 Wood lath and plaster must be reattached to existing joists or rafters in a manner approved by the building official.
3 Stresses given may be increased for combinations of loads as specified in Section 17.40.320.
e. Exception: The wall may be supported by flexible bracing members designed in accordance with Section 17.40.320B of this part if the deflection at design loads is not less than one-quarter nor more than one-third of the wall thickness at the level under consideration.
f. All vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one-half the unsupported height of the wall nor ten feet, whichever is less.
g. The wall height may be measured vertically to bracing elements other than a floor or roof. Spacing of bracing elements and wall anchors shall not exceed six feet. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by components of vertical displacements of the floor or roof.
2. a.
Veneer. Veneer shall be anchored with approved anchor ties, conforming to the required design capacity specified in Section 3004(c) of the 1985 Uniform Building Code, and placed at a maximum spacing of twenty-four inches.
b. Exception: Existing veneer anchor ties may be acceptable provided the ties are in good condition and conform to the minimum size, maximum spacing and material requirements as indicated below. The veneer anchor ties shall be corrugated galvanized iron strips not less than one inch in width, eight inches in length and one-sixteenth of an inch in thickness and shall be located and laid in every alternate course in the vertical height of the wall at a spacing not to exceed seventeen inches on center horizontally. As an alternate, the spacing may be every fourth course vertically at a spacing not to exceed nine inches on center horizontally.
c. The existence and condition of existing veneer anchor ties shall be verified as follows:
i. An approved testing laboratory shall verify the location and spacing of the ties and shall submit a report to the building official for approval as a part of the structural analysis.
ii. The veneer in a selected area shall be removed to expose a representative sample of ties (not less than four) for inspection by the building official.
iii. Existing Roof, Floors, Walls, Footings, and Wood Framing. Existing materials, including wood shear walls, may be used as a part of the lateral load resisting system, provided that stresses in these materials do not exceed the values shown in Table No. 2.
C. Strengthening of Existing Materials: New materials, including wood shear walls may be utilized to strengthen portions of the existing seismic resisting system provided that stresses do not exceed the values shown in Table No. 3.
TABLE NO. 3
ALLOWABLE VALUES OF NEW
MATERIALS USED IN CONJUNCTION
WITH EXISTING CONSTRUCTION
New Materials or Configuration of Materials | Allowable Values
1. Horizontal diaphragms
Plywood sheathing applied directly over existing straight sheathing with ends of plywood sheets bearing on joists or rafters and edges of plywood located on center of individual sheathing boards. | Same as specified in Table 25-J of the 1985 Uniform Building Code for blocked diaphragms.
2. Shear walls
a. Plywood sheathing applied directly over existing wood studs. (No value shall be given to plywood applied over existing plaster or wood sheathing boards.) | Same as values specified in Table No. 25-K of the 1985 UBC for shear walls.
b. Dry wall or plaster applied directly over existing wood studs. | 75 percent of the values specified in Table No. 47-I of the 1985 UBC.
c. Dry wall or plaster applied to plywood sheathing over wood studs. | One-third of the values specified in Table No. 47-I of the 1985 UBC.
3. Shear bolts
Shear bolts and shear dowels embedded a minimum of 8 inches into unreinforced masonry walls. Bolt centered in a 2-1/2-inch diameter hole with dry-pack or nonshrink grout around the circumference of the bolt. 1, 3 | 133 percent of the values for plain masonry specified in Table No. 24-J of the 1985 UBC. No values larger than those given for 3/4-inch diameter bolts shall be used.
4. Tension bolts
Tension bolts and tension dowels extending entirely through URM walls secured with bearing plates on far side of wall with at least 30 square inches of area. 2 | 1,200 pounds per bolt.
5. Combination shear and tension wall anchors
a. Bolts extending to the exterior face of the wall with a 2-1/2-inch round plate under the head. Install as specified for shear bolts. Spaced not closer than 12 inches on centers. 1, 2, 3 | 600 lbs. per bolt for tension. 4 See item 3 (shear bolts) for shear values.
b. Bolts or dowels extending to the exterior face of the wall with a 2-1/2-inch round plate under the head and drill at an angle of 22-1/2 degrees to the horizontal. Install as specified for shear bolts. 1, 2, 3 | 1200 lbs. per bolt or dowel for tension. 4 See item 3 for shear values.
c. Through bolt with bearing plate for tension per item 4. Combined with minimum 8-inch grouped section for shear per item 3. | See item 4 (tension bolts) for tension values. 4 See item 3 for shear values.
6. Infilled walls
Reinforced masonry infilled openings in existing unreinforced masonry walls with keys or dowels to match reinforcing. | Same as values specified for unreinforced masonry walls in this chapter.
7. Reinforced masonry
Masonry piers and walls reinforced as specified in Chapter 24 of the 1985 Uniform Building Code. | Same as values specified in Table No. 24-B of the 1985 Uniform Building Code.
8. Reinforced concrete
Concrete footings, walls and piers reinforced as specified in Chapter 26 and designed for tributary loads. | Same as values specified in Chapter 26 of the 1985 Uniform Building Code.
9. Existing foundation loads
Foundation loads for structures exhibiting no evidence of settlement. | Calculated existing foundation loads due to maximum dead load plus live load may be increased by 25 percent and may be increased 50 percent for dead load plus seismic loads required by this chapter.
1 Bolts and dowels to be tested as specified in Section 17.40.300E.
2 Bolts and dowels to be 1/2-inch diameter minimum.
3 Drilling for bolts and dowels shall be done with an electric rotary drill. Impact tools shall not be used for drilling holes or tightening anchor and shear bolt nuts.
4 Allowable bolt and dowel values specified are for installations in minimum three wythe wall. For installations in two wythe walls use fifty percent of the value specified, except that no value shall be given to tension bolts that do not extend entirely through the wall and are secured with bearing plates on the far side.
D. Minimum Acceptable Quality of Existing Unreinforced Masonry Walls:
1. General Provisions. All unreinforced masonry walls utilized to carry vertical loads and seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this subsection. All masonry quality shall be equal or exceed the minimum standards established herein or shall be removed and replaced by new materials. The quality of mortar in all masonry walls shall be determined by performing in-place shear tests. Alternate testing methods may be approved by the building official upon submission of adequate evidence to indicate its equivalence. The vertical wall joint between wythes (collar joint) shall be inspected at each test location after the in-place shear tests, and an estimate of the percentage of wythe-to-wythe mortar coverage shall be reported along with the results of the in-place shear tests. Where the exterior face is veneer, the type of veneer, its thickness and its bonding and/or ties to the structural wall masonry shall also be reported. Nothing shall prevent the pointing with mortar of all the masonry wall joints before the tests are first made. Prior to any pointing, the mortar joints must be raked and cleaned to remove loose and deteriorated mortar. Mortar for pointing shall be Type S or N except masonry cements shall not be used. All preparation and mortar pointing shall be done under the continuous inspection of a special inspector. At the conclusion of the inspection, the inspector shall submit a written report to the person responsible for the seismic analysis of the building setting forth the results of the work inspected. Such report shall be submitted to the building official for approval as part of the structural analysis. All testing shall be performed in accordance with the requirements specified in this section by an approved agency. An accurate record of all such tests and their location in the building shall be recorded and these results shall be submitted to the building official for approval as part of the structural analysis.
2. Number and Location of Tests. The minimum number of tests shall be as follows:
a. At each of both the first and top stories, not less than two per wall line or line of wall elements providing a common line of resistance to lateral forces.
b. At each of all other stories, not less than one per wall element providing a common line of resistance to lateral forces.
c. In any case, not less than one per fifteen hundred square feet of wall surface and a total of eight.
The shear tests shall be taken at locations representative of the mortar conditions throughout the entire building, taking into account variations in workmanship at different building height levels, variations in weathering of the exterior surfaces, and variations in the condition of the interior surfaces due to deterioration caused by leaks and condensation of water and/or by the deleterious effects of other substances contained within the building. Where the higher h/t ratios allowed in footnotes 3 and 4 of Table No. 1 of Section 17.40.320 F.1.b. are to be utilized, all the in-place shear tests taken at the top story shall be included in the eighty percent of the shear tests uses to determine the minimum mortar shear strength. The exact test locations shall be determined at the building site by the person responsible for the seismic analysis of the subject building.
3. In-Place Shear Tests. The bed joint of the outer wythe of the masonry wall shall be tested in shear by laterally displacing a single brick relative to the adjacent bricks in the wythe. The opposite head joint of the brick to be tested shall be removed and cleaned prior to testing. The minimum quality mortar in eighty percent of the shear tests shall not be less than the total of thirty psi plus the axial stress in the wall at the point of the test. The shear stress shall be based on the gross area of both bed joints and shall be that at which movement of the brick is first observed.
E. Testing Shear Bolts.
1. One-fourth of all new shear bolts and dowels embedded in unreinforced masonry walls shall be tested by a special inspector using a torque calibrated wrench to the following minimum torques:
a. 1/2-inch diameter bolts or dowels = 40 foot-pounds.
b. 5/8-inch diameter bolts or dowels = 50 foot-pounds.
c. 3/4-inch diameter bolts or dowels = 60 foot-pounds.
2. No bolts exceeding 3/4-inch diameter shall be used. All nuts shall be installed over malleable iron or plate washers when bearing on wood and heavy cut washers when bearing on steel.
F. Determination of Allowable Stresses for Design Methods Based on Test Results.
1. Design Shear Values. Design seismic in-plane shear stresses shall be substantiated by tests performed as specified in subsection D.3 of this section. Design stresses shall be related to test results obtained in accordance with Table No. 4. Intermediate values between five and ten psi may be interpolated.
TABLE NO. 4
ALLOWABLE SHEAR STRESS. FOR TESTED
UNREINFORCED MASONRY WALLS
80 Percent of Test Results, in psi, Not Less Than | Average Test Result of Cores in psi | Seismic In-Plane Shear Based on Gross Area
30 plus axial stress | 20 | 3 psi*
40 plus axial stress | 27 | 4 psi*
50 plus axial stress | 33 | 5 Psi*
100 plus axial stress | 67 or more | 10 psi max*
* Allowable shear stress may be increased by addition of 10 percent of the axial stress due to weight of wall directly above.
2. Design Compression and Tension Values. Compression stresses for unreinforced masonry having a minimum design shear value of three psi shall not exceed one hundred psi. Design tension values for unreinforced masonry shall not be permitted.
G. Existing Wall Anchors. Five percent of the existing wall anchors utilized as all or part of the required wall anchors shall be tested in pullout by an approved testing agency. The minimum number tested shall be four per floor, with two tests at walls with joist parallel to the wall. The test apparatus shall be supported on the masonry wall at a minimum distance equal to the wall thickness from the anchor tested. The rod anchor shall be given a preload of three hundred pounds prior to establishing a datum for recording elongation. The tension test load reported shall be recorded at 1/8-inch relative movement of the anchor and the adjacent masonry surface. Results of all tests shall be reported. The report shall include the test results as related to the wall thickness and joist orientation. The allowable resistance value of the existing anchors shall be forty percent of the average of those tested anchors having the same wall thickness and joist orientation.
H. Qualification Tests. Qualification tests for new devices used for wall anchorage shall be tested with the entire tension load carried on the enlarged head at the exterior face of the wall. Bond on the part of the device between enlarged head and the interior wall face shall be eliminated for the qualification tests. The resistance value assigned the device shall be twenty percent of the average of the ultimate loads.