SEC. 11-721. - DEAD-END CORRIDORS.

An existing dead-end corridor which exceeds 20 feet in length and serves the occupants of a living quarter may remain, provided the dead-end corridor complies with all of the following: (a) The dead-end corridor shall be constructed as described above for the full length of the dead-end corridor. (b) The dead-end corridor shall not exceed 40 feet in length. (c) A door with a magnetic hold-open device shall be placed across the corridor to create a vestibule located furthest from the open end of the dead-end corridor. The placement of the door shall be located not more than 20 feet from the open end of the dead-end corridor and the occupant load of the vestibule shall be less than 10 occupants.

(Added Ord. 2007-102, § 1, eff. 1-20-08).