For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-28-604.3 — Covering and linings

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-604.3

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/05c1d805-7010-4a5d-9277-64a000d845c8

18-28-604.3 Covering and linings.

Coverings and linings, including adhesives when used, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50, when tested in accordance with ASTM E 84. Duct coverings and linings shall not flame, glow, smolder or smoke when tested in accordance with ASTM C 411 at the temperature to which they are exposed in service. The test temperature shall not fall below 250°F (12 1°C).

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.