§ 18-28-604.3 — Covering and linings
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-604.3
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/05c1d805-7010-4a5d-9277-64a000d845c8
18-28-604.3 Covering and linings.
Coverings and linings, including adhesives when used, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 50, when tested in accordance with ASTM E 84. Duct coverings and linings shall not flame, glow, smolder or smoke when tested in accordance with ASTM C 411 at the temperature to which they are exposed in service. The test temperature shall not fall below 250°F (12 1°C).