§ 30.16 — OIL TANKS AND PIPING
Madison General Ordinances (Rev. 28, Update 3: codified through ORD-26-00040, published August 3, 2026) · Madison General Ordinances § 30.16
Corpus is an independent public-information project, not the official City of Madison website. Stable reference: corpuslaw.us/code/05fd8941-dda2-4491-9546-c4ee95ec7c37
30.16 - OIL TANKS AND PIPING.
(1) Gravity supply tanks shall not exceed two hundred seventy-five (275) gallons individual capacity. Each tank shall be valved independently. Where oil is supplied to the burner by gravity and a constant level device is not incorporated in the burner assembly or in an auxiliary tank used in connection with an automatic pump, an approved constant level device shall be installed in the oil feed line at the gravity tank or as close thereto as practicable. The vent openings of such constant level device shall be connected by piping or tubing to outside the building unless the constant level device is provided with an approved anti-flooding device. Vent pipes or tubing of constant level devices shall not be connected to tanks or tank vents. (2) Pressure tank feed shall be used only with burners arranged to prevent abnormal discharge of oil at the burner by automatic means specifically approved for the burner with which it is used. Pressure tanks shall not exceed a capacity of sixty (60) gallons and shall not be operated at pressure exceeding fifty (50) pounds per square inch. They shall be equipped with a reliable pressure gauge and with an automatic relief valve piped to discharge outside of buildings. (3) Installation of Underground Tanks. All underground tanks shall comply with SPS 38 Wisconsin Flammable and Combustible Liquids Code. Tank owners must also comply with the U.S. Environmental Protection Agency, Regulations for Underground Storage Tanks Systems. (R. & Re-Cr. by Ord. 10,255, Adopted 5-7-91; Am. by ORD-12-00035, 3-28-12) (4) Installation of Tanks Inside Buildings. Oil supply tanks larger than sixty (60) gallons capacity shall not be located in buildings above the lowest story, cellar or basement. Unenclosed inside storage tanks and auxiliary tanks shall not be located within five (5) feet, horizontally, of any fire or flame. Inside storage and auxiliary tanks shall be securely supported by substantial incombustible supports to prevent settling or sliding. Oil supply tanks located inside buildings shall not exceed two hundred seventy-five (275) gallons individual capacity or five hundred fifty (550) gallons aggregate capacity. Tanks exceeding two hundred seventy-five (275) gallons individual capacity or one thousand one hundred (1,100) gallons aggregate capacity in an individual building or in a section of a building separated by fire walls shall be installed in an enclosure constructed as follows: The walls of the enclosure shall be constructed of reinforced concrete at least six (6) inches thick or of brick at least eight (8) inches thick. Such enclosures shall be installed only on concrete or other fire-resistive floors and shall be bonded to the floors. Enclosures shall have tops of reinforced concrete at least five (5) inches thick or equivalent fire-resistive construction, except that where floor or roof construction above the enclosure is concrete or other fire-resistive construction, the walls may be extended to and bonded to the underside of the construction above, in lieu of the provision of a separate top. Any openings to such enclosures shall be provided with fire doors or other approved closures and six (6) inch, noncombustible liquid-tight sills or ramps. (5) Construction of Tanks. Underground tanks and tanks inside buildings shall be constructed of steel or wrought iron of a minimum gauge (U.S. Standard) in accordance with the following table, except that for tanks of one hundred eighty-one (181) to two hundred seventy-five (275) gallons capacity, installed in buildings, and without masonry enclosure, the minimum gauge shall be No. 14. Capacity Gals. | Minimum Thickness | Vent Size | Minimum Distance to Lines of Adjoining Property or Nearest Building 1 to 300 | 14 Gauge | 1¼" | 1 Foot 301 to 560 | 14 Gauge | 1¼" | 1 Foot 561 to 1,100 | 14 Gauge | 1¼" | 1 Foot Joints shall be riveted and caulked, brazed, welded or made tight by some equally satisfactory process. Tanks shall be tight and sufficiently strong to bear without injury, the most severe strains to which they may be subjected in practice. Shells of tanks shall be properly reinforced where connections are made. All connections to underground tanks, outside tanks aboveground, and tanks inside buildings shall be made through the top of the tank above the liquid level, except that tanks of not over two hundred seventy-five (275) gallons capacity may have one bottom connection for gravity feed and one opening for an approved key stem gate valve to facilitate cleaning or for a scavenging line to be run to the outside and capped oil tight when not in use. Pressure tanks shall be designed for at least six (6) times the maximum working pressure. Tanks shall be thoroughly coated on the outside with tar, asphaltum, or other suitable rust-resisting paint. Where placed in corrosive soil, special protection may be required. Note. Tanks labeled by Underwriters' Laboratories have been tested and examined for compliance with these regulations and detailed standards covering their design and construction. The construction and installation of all tanks having a capacity of five thousand (5,000) gallons and larger shall be submitted to the Department of Safety and Professional Services for approval (SPS 310.1). This information shall be forwarded to the Fire Prevention Bureau. For fuel oil heavier than thirty-five (35) degrees A.P.I., tanks may be made of concrete, in accordance with the regulations of the National Board of Fire Underwriters for the Construction of Concrete Fuel Oil Storage Tanks as recommended by the National Fire Protection Association. (Am. by Ord. 12,322, Adopted 2-2-99; ORD-12-00035, 3-28-12) (6) Tank Vents. Storage tanks shall be equipped with an open vent or an approved automatically operated vent, arranged to discharge to the open air. Vent openings and vent pipes shall be of ample size to prevent abnormal pressure in the tank during filling but not smaller than one and one-fourth (1¼) inches pipe size. See table under Section 30.16(5). Vent pipes shall be arranged to drain to the tank. The lower end of the vent pipe shall not extend through the top into the tank for a distance of more than one (1) inch. Vent pipes shall terminate outside of buildings at a point not less than two (2) feet distant from any window or other building opening and not less than twenty-four (24) inches above the ground. Outer ends of vent pipes shall be provided with a weatherproof hood with screen. Vent pipes of tanks containing heaters shall be extended to such a height that oil vapors discharging from the vent will be readily diffused without danger of ignition. Provided, however, that combination fill and vent fittings approved by the Building Inspector may be used if located not less than two (2) feet distant from any window or other building opening and less than twenty-four (24) inches above the ground. Vent pipes shall not be cross-connected with fill pipes or return lines from burners. Fill and vent pipes shall not be run through windows or coal chutes unless such openings are totally enclosed with masonry to prevent oil from entering building during filling operations. (7) Tank Fill and Overflow Pipes. Underground tanks and storage tanks inside the buildings shall be filled only through fill pipes terminating outside of buildings at a point at least two (2) feet from any building opening at the same or lower level. Fill terminals shall be closed tight, when not in use by a metal cover designed to prevent tampering. The fill pipe shall be located below the vent pipe. Auxiliary tanks shall be filled by pumping from storage tanks. Auxiliary tanks other than vacuum tanks shall be equipped with an overflow pipe draining to the storage tank, at least one (1) size larger than the supply pipe. Overflow pipes of auxiliary gravity tanks shall have no valves or obstructions. Overflow pipes of auxiliary pressure tanks shall be provided with interconnected valves or other means for automatically venting the tank during filling. (8) Oil Gauging. All tanks in which a constant oil level is not maintained by an automatic pump shall be equipped with an approved method of determining the oil level. Test wells shall not be installed inside buildings and where permitted for outside services, shall be closed tight when not in use by a metal cover designed to prevent tampering. Gauging devices such as liquid level indicators or signals shall be installed so that oil or vapor will not be discharged into the building from the fuel supply system. No glass gauge or any gauge, the breaking of which will permit oil to escape from the tank, shall be used. (9) Oil Pumps. Oil pumps shall be of an approved type, secure against leaks, and shall be rigidly fastened in place. Automatic pumps not an integral part of the burner, shall be arranged to stop automatically in case of total breakage of the supply line to the burner. In isolated locations, where fire protection equipment is dependent upon a heating plant fired by an oil burner, oil pumps supplying the burner shall be installed in duplicate. (10) Piping. All piping shall be standard full weight wrought iron, steel or brass pipe with standard fittings or approved brass or copper tubing with approved fittings, except that an approved flexible metal hose may be used for reducing the effects of jarring and vibration or where rigid connections are impracticable. No sweat joints shall be used on any oil lines including vent and fill pipe. (11) Oil Lines. Domestic and Commercial Fuels. Any oil line for burners using a catalytic or universal fuel oil of No. 3 grade or lighter, drawing from an outside tank may use three-eighths (⅜) or one-fourth (¼) O.D. copper tubing or equal on runs of forty (40) feet or less. For fuel lines longer than forty (40) feet, one-half (½) inch O.D. copper shall be used. Oil lines to an outside underground tank shall consist of one (1) suction line and one (1) return line. Oil supply lines to burners shall be provided with approved filter. Where pumping from a tank on multiple burner installations, each burner must have its own suction line but may be connected to a common return line. All oil lines shall be carefully protected against mechanical injury in a manner satisfactory to the Director of the Building Inspection Division. (12) Valves. Readily accessible shut-off valves of approved type shall be installed in oil supply line near each burner and close to gravity and pressure supply tanks. Shut-off valves of approved type shall be installed on the discharge and suction side of oil pumps which pump directly to the burner but which are not a part of the burner unit. Where a shut-off valve is installed in the discharge line of an oil pump, an approved pressure relief valve shall be connected into the discharge line between the pump and the shut-off valve and arranged to return surplus oil to the storage tank or to bypass it around the pump. (13) Gas Pilots on Oil Burner. Line supplying gas pilots for oil burning appliances shall be accessible and not less than one-half (½) inch standard wrought iron or steel pipe size and shall not be exposed to extreme temperature.
(Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08)
Ask a question about Madison law
Corpus searches the Madison sections it holds and shows the ones that match, with their citations. Free, no sign-in.