§ 18-29-314.2.2 — Drain pipe materials and sizes

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-314.2.2

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/1e5e415a-3d46-407e-b785-03aaee7f778c

18-29-314.2.2 Drain pipe materials and sizes.

Components of the condensate disposal system shall be cast iron, galvanized steel, copper and copper alloy, cross-linked polyethylene, polyethylene, CPVC, PVC or polypropylene pipe or tubing. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 relative to the material type. Condensate waste and drain line size shall be not less than 3/4-inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 18-29-314.2.2. Table 18-29-314.2.2 Condensate Drain Sizing EQUIPMENT CAPACITY | MINIMUM CONDENSATE PIPE DIAMETER Up to 20 tons of refrigeration | 3/4 inch Over 20 tons to 40 tons of refrigeration | 1 inch Over 40 tons to 90 tons of refrigeration | 1 1/4 inch Over 90 tons to 125 tons of refrigeration | 1 1/2 inch Over 125 tons to 250 tons of refrigeration | 2 inch For SI: 1 inch = 25.4 mm, 1 ton of capacity = 3.517 kW. (Added Coun. J. 10-14-21, p. 37722, Art. III, § 24)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.