SEC. 11-710. - SMOKE CONTROL SYSTEM.

Existing high-rise buildings shall provide a smoke control system in all portions of the building including basements. The smoke control system shall meet the requirements of C.B.C. Section 905 or all the requirements of this division. EXCEPTION: The following areas are exempt: (1) New or existing rooms less than 50 square feet in area. (2) New or existing rooms located at or above grade level provided the room has a direct exit to the exterior of the building. (3) Floor levels with open able windows or breakable tempered glass panels in the exterior walls. The area of the open able windows or panels shall not be less than 20 square feet per 50 linear foot interval around the building perimeter. Tempered glass panels shall have no coating or film applied which will modify its' breaking characteristics. Panels shall be identified in a manner approved by the Fire Department.

(Added Ord. 2007-102, § 1, eff. 1-20-08).