For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 913.2.3 — Integrity of the fire pump room

San Francisco Administrative Code (2026 S-96: through Ordinance 133-26, File No. 260686, approved July 23, 2026, effective August 23, 2026) · SF Fire Code § 913.2.3

Corpus is an independent public-information project, not the official City of San Francisco website. Stable reference: corpuslaw.us/code/378006f7-80af-450d-9799-dd2ecce320c5

913.2.3. Integrity of the fire pump room.

The integrity of the fire pump room shall not be compromised. All non-fire pump related equipment, piping, drains, electrical equipment, and electrical services shall not be routed through or located within the fire pump room. Examples include, but are not limited to: 1. Non-fire water system piping 2. Domestic water equipment and piping 3. Drain piping 4. HVAC equipment, ducts, fans, and piping 5. Boilers or furnaces, fuel equipment, and piping (unless feeding a diesel fire pump motor) 6. Electrical equipment and service (e.g. Transformers and switchgear)

Ask a question about San Francisco law

Corpus searches the San Francisco sections it holds and shows the ones that match, with their citations. Free, no sign-in.