913.2.3. Integrity of the fire pump room.
The integrity of the fire pump room shall not be compromised. All non-fire pump related equipment, piping, drains, electrical equipment, and electrical services shall not be routed through or located within the fire pump room. Examples include, but are not limited to: 1. Non-fire water system piping 2. Domestic water equipment and piping 3. Drain piping 4. HVAC equipment, ducts, fans, and piping 5. Boilers or furnaces, fuel equipment, and piping (unless feeding a diesel fire pump motor) 6. Electrical equipment and service (e.g. Transformers and switchgear)