914.3.2.2.1. Drain ejector pumps (Sump Pumps).
Drain ejector pumps shall be permitted to manage fire water tank overflow. Ejector pumps are only to be used when gravity drainage is not available (CPC 709.1). Where overflow lines route to a drain-ejector pump, the following shall apply: 1. Redundant or backup drain ejector pump(s) shall be provided. 2. All drain ejector pumps shall be installed in a remote location approved by the Fire Department and shall not be located inside or near a fire pump room. 3. All drain ejector pumps shall be sized and rated for the maximum fill flow rate of the water tank. 4. All drain ejector pumps shall be provided with approved emergency/standby power. 5. All drain ejector pumps shall discharge to a safe location that will not subject any portion of the building to flooding.