905.2.1. Local Installation Standard.

Standpipe systems shall be installed using 3-inch (76.2 mm) national standard hose thread. Each standpipe outlet shall be placed to provide a minimum of six inches on all sides of the handle and 18 inches on all sides of the outlet or located as approved by the fire code official.