For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-28-606.4 — Controls operation

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-606.4

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/4c924de1-d7aa-4033-b354-2073de3a0842

18-28-606.4 Controls operation.

Upon activation, the smoke detectors shall shut down the air distribution system through a hard-wired interlock between the fans and the smoke detector, not through programming. Air distribution systems that are part of a smoke control system shall be controlled in accordance with Section 909 and Appendix S of the Chicago Building Code. (Amend Coun. J. 11-9-16, p. 36266, § 36; Amend Coun. J. 4-10-19, p. 100029, Art. XII, § 10; Amend Coun. J. 9-14-21, p. 35949, Art. VI, § 8)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.