Sec. 26-332. - Installation standards and type of assembly required.
(a) Backflow prevention assemblies shall be installed in accordance with the following requirements: (1) Backflow prevention assemblies shall be installed in accordance with all applicable laws; (2) Backflow prevention assembly installers shall obtain the required plumbing permits prior to installation; (3) No part of an RP shall be submerged in water or installed in a location subject to flooding; (4) If a fire DC is installed below grade, non-ferrous plugs shall be maintained in the test ports at all times and adequate drainage shall be provided; (5) All backflow prevention assemblies shall be protected from freezing and other severe weather conditions; (6) All vertical backflow assembly installations must be approved in writing by the director prior to installation; (7) If a backflow assembly is installed four (4) feet or higher above the floor, it shall be equipped with a rigidly and permanently installed platform with fixed access. This installation shall also meet all applicable requirements set forth in the Occupational Safety and Health Act (29 U.S.C. Ch. 15) and State of Texas occupational safety and health laws; and (8) Backflow prevention assemblies may only be installed in vaults that are kept reasonably free of silt and debris and contain a floor drain for proper drainage. (b) Variances from the requirements in section 26-332(a) require written approval from the director and will be evaluated on a case-by-case basis. (c) The type of backflow prevention assembly required by the regulatory authority shall be commensurate with the degree of hazard that exists on the premises. The minimum types of backflow prevention assemblies required to protect the public water system are set forth in Table 1 and Table 2 below; however, the user may choose a higher level of backflow protection than required by the city. Table 1 - Point-of-Use Isolation Health Hazard Installations | Type of Approved Backflow Prevention Assembly Required Aspirators | RP, PVB, or SVB Autoclave | RP Autopsy and mortuary equipment | RP, PVB, or SVB Bedpan washers | RP, PVB, or SVB Carbonated Drink Machines | RP-Stainless Steel Assembly and all downstream piping shall be noncorrosive when in contact with CO2 gas Chemical Dispensers | AG, RP, PVB, or SVB Connection to industrial fluid systems | RP Connection to plating tanks | RP Connection to salt-water cooling systems | RP Connection to sewer pipe | AG Cooling towers with chemical additives | RP or AG Cuspidors | RP, PVB, or SVB Domestic space heating boiler | RP Dye vats or machines | RP Fire-fighting system (toxic liquid foam concentrates) | RP Flexible shower heads | AVB, RP, PVB, or SVB Heating equipment commercial | RP Heating equipment domestic | RP Hose bibs (untestable) | AVB or HBVB Irrigation systems on properties with OSSFs | RP Commercial dishwashers | RP Disposals or grinders with water connections | RP Lab bench equipment | RP, PVB, or SVB Ornamental fountains | RP, PVB, or SVB Pitcher, cup, or glass washers | AG or RP Swimming pools - Public | RP Swimming pools - Private | RP Sewage pump | AG Sewage ejectors | AG Shampoo basins | RP, PVB, or SVB Specimen tanks | RP, PVB, or SVB Steam generators | RP Steam tables | RP, PVB, or SVB Sterilizers | RP Tank vats or other vessels containing toxic substances | RP Trap Primers | AG Vending machines | RP, PVB, or SVB Water Filters—Commercial | RP Water Filters—Residential R/O or Whole home | RP Water Softeners | RP Watering troughs | AG, PVB, or SVB Note: Situations not covered in Table 1 will be evaluated on a case-by-case basis, and the required Backflow Prevention Assembly shall be determined by the director. Note: Commercial in-line filters currently protected with DCs may continue to be served by current Backflow Protection until the assembly is no longer repairable in-line, at which time it must be upgraded to an RP. Table 2 - Containment Type of Hazard | Minimum Type of Approved Backflow Prevention Assembly Required on a Domestic Service Line Fire protection systems utilizing chemicals or additives | RPDA Non-Residential and Residential fire sprinkler systems without chemicals or additives (new installations or remodels of existing systems only) | DCDA or RPDA Commercial landscape irrigation systems | RP or PVB Commercial landscape irrigation systems with chemical additives | RP Private Water System associated with Domestic Use systems on all new non-residential construction | RP Stationary Construction Fire Hydrant Meters | RP Service Connections where any person or governmental entity is purchasing Potable Water Supply for the purpose of resale or distribution | RP or AG at each service connection New Construction on Premises owned by any state, federal, or foreign government or agency | RP or RPDA New Construction on Premises that are outside the City of Denton Corporate Boundaries | RP or RPDA Animal Watering Sites | AG, RP, PVB, or SVB. However, PVB and SVB are not approved for use in situations where Backpressure exists. Premises with Auxiliary Water Supply | RP or RPDA
(Ord. No. 25-1726, § 3(Exh. A), 3-24-26)
Ask a question about Denton law
Corpus searches the Denton sections it holds and shows the ones that match, with their citations. Free, no sign-in.