§ 30.09 — WARM AIR SUPPLY DUCTS

Madison General Ordinances (Rev. 28, Update 3: codified through ORD-26-00040, published August 3, 2026) · Madison General Ordinances § 30.09

Corpus is an independent public-information project, not the official City of Madison website. Stable reference: corpuslaw.us/code/53cc9432-7774-4113-a9d1-d5e107e85f7a

30.09 - WARM AIR SUPPLY DUCTS.

(1) Materials. All gravity and forced warm air ducts shall be constructed entirely of noncombustible material equivalent in structural strength and durability to the following: (a) Metal Gauges: Ducts Not Enclosed in Partitions. ROUND DUCTS Diameter Inches | Minimum Wt. of Tin | Minimum Thickness Galv. Iron U.S. Gauge | Minimum Thickness Aluminum B & S Gauge Less than 12 or more | 121C (107 lb.) | 30 | 26 1X (135 lb.) | 28 | 26 RECTANGULAR DUCTS Width Inches | Minimum Thickness Galv. Iron U.S. Gauge | Minimum Thickness Aluminum B & S Gauge Less than 14 | 28 | 26 14 or more | 26 | 24 (b) Metal Gauges: Ducts Enclosed in Partitions. Width | Minimum Weight of Tin | Minimum Thickness Galv. Iron U.S. Gauge | Minimum Thickness Aluminum B & S Gauge 14 or less | 1C (107 lb.) | 30 | 26 Over 14 | 1X (135 lb.) | 28 | 26 (2) Supply Ducts in Concrete Slab. All supply ducts shall be completely encased in not less than two (2) inches of concrete. Where the slab is less than two (2) feet below grade, edge insulation consisting of at least one (1) inch thickness of waterproof insulation shall be installed to a depth of at least two (2) feet. Insulation shall be placed in back of all boots. (3) Vibration Isolation. Vibration isolation connectors in duct systems shall be made of woven asbestos or approved flameproofed fabric or shall consist of sleeve joints with packing of rope asbestos or other approved incombustible material. Vibration isolation connectors of fabric shall not exceed ten (10) inches in length. (4) Cross Braking. All gravity or forced warm air ducts, eighteen (18) inches or wider, and forty-eight (48) inches or over in length, shall be cross braked on top and bottom and shall have standing seams or angle iron braces. (5) Ducts Through Masonry. No warm air duct, round or rectangular, shall come in tight contact with cold masonry walls. (6) Duct Linings. Linings used inside of ducts shall be fire-resistive. Note: The use of flameproof fabric of metal or mineral and listed in Building Materials List published by Underwriters' Laboratories, Inc. is acceptable. (7) Joints and Seams. Joints and seams of all ducts shall be securely fastened and made substantially air tight. Slip joints shall have a lap of at least one (1) inch, and be individually fastened. Tape used for sealing joints shall be no more combustible than approved flameproof fabric. All joints shall be s and drive cleat or snap lock. (8) Duct and Riser Supports. All ducts and risers shall be securely supported by metal hangers, straps, lugs or brackets. No nails shall be driven through the duct or riser walls and no unnecessary holes shall be cut therein. (9) Riser Installation. All risers shall be tightly fitted and supported in a proper manner so as not to obstruct the flow of air, but to retain the full capacity throughout. Warm air baseboard risers shall extend through the finished floor at least three-eighths (3/8) inch and shall be securely fastened into baseboard section. (10) Removal of Firestopping for Ducts. Where the installation of ducts in walls, floor or partitions require the removal of any fire-stopping, the spaces around the duct at such points where fire-stopping was removed shall be tightly filled or sealed with incombustible materials. (11) Insulation of Warm Air Ducts for Gravity and Forced Air. Ducts located in cold attic spaces, garages with rooms above or adjacent to it, or other equivalent cold spaces, shall be insulated with at least one (1) inch thickness of insulation, and an inspection shall be made of the insulation before the work is concealed. (12) Insulation of Warm Air Ducts for Gravity and Forced Air. Ducts located in cold spaces, garages with rooms above or adjacent to it, or other equivalent cold spaces, shall be insulated with at least one (1) inch thickness of insulation and an inspection shall be made of the insulation before the work is concealed. (13) Volume Dampers - Forced Air Systems. Volume dampers of locking type shall be placed in each forced warm air run. Where warm air runs are concealed, the dampers will not be required but volume control dampers will be required in each branch duct and a damper shall be installed in each register or baseboard section. Outside air intake ducts shall be equipped with volume dampers.

Ask a question about Madison law

Corpus searches the Madison sections it holds and shows the ones that match, with their citations. Free, no sign-in.