§ 30.25 — CONTROL SYSTEMS FOR AUTOMATIC FIRING EQUIPMENT
Madison General Ordinances (Rev. 28, Update 3: codified through ORD-26-00040, published August 3, 2026) · Madison General Ordinances § 30.25
Corpus is an independent public-information project, not the official City of Madison website. Stable reference: corpuslaw.us/code/5f662ba0-1a32-4dc9-8d05-41324af0dfdb
30.25 - CONTROL SYSTEMS FOR AUTOMATIC FIRING EQUIPMENT.
(1) General. All systems shall have one (1) operating control to control temperature for furnace or pressure for boilers. Each system shall have, in addition, one (1) high limit control. These controls shall be one hundred twenty (120) volts, one (1) side grounded and shall be wired into the ungrounded line (except where self-generating controls are used). In addition, all steam boilers shall have a low water cutoff and all hot water boilers over two hundred thousand (200,000) BTU input shall be equipped with a low water cutoff. The above-mentioned control shall be wired into the circuit ahead of all other controls or relays. All motors of one-eighths (⅛) HP and larger used in conjunction with any heating, ventilating, or air conditioning equipment shall be on its own circuit. Each motor shall be protected by a proper Type S time delay fuse, except that fractional horse power motors for circulating pumps, unit ventilators, etc. may be grouped on a motor branch circuit. If the motors for the circulating pumps, unit ventilators, etc. are provided with integral thermal overload protection, external over-current protection will not be required. All heating, ventilating, and air conditioning units shall have an electrical disconnect located within ten (10) feet and in sight of the unit. (2) Relief Valves. All boilers shall have an A.S.M.E. approved pressure relief valve rated at the full gross rating of the boiler input. There shall be no valves between the boiler and the relief valve. The discharge from the water relief valve and the discharge from the low water cutoffs shall be piped full size to within eighteen (18) inches of the floor. (3) Draft Controls. All automatically fired natural draft equipment shall have either barometric or mechanical draft control equipment installed in the boiler breeching. Gas-fired boilers or furnaces may use approved draft hoods, mechanical draft control or barometric draft regulators. Barometric draft regulators used on gas-fired equipment must be free-swinging with no stops within one hundred eighty (180) degrees from the pivot point. No barometric damper, draft hood or sensor for mechanical draft control shall be located in any space other than where the burner is drawing combustion air. (4) Stoker Controls. Stoker-fired steam boilers with zone valves shall have a reverse acting pressure control or aquastat to open one of the zone valves at a pressure or temperature below the setting of the high limit control. On water boilers, there shall be reverse acting submerged type aquastat to open the zone valve and/or start a circulating pump below the setting of the high limit control. On a furnace with zone control or fan system, there shall be a reverse acting airstat to open a zone damper and/or turn on the fan below the setting of the high limit control. All stokers shall be equipped with a timing device to operate the stoker a minimum of one (1) minute every thirty (30) minutes during the off period. All bin feed type stokers shall have out-fire control. (5) Retrofit Controls and Devices. Controls or devices installed on all gas fired heating equipment shall be certified by American Gas Association (A.G.A.) or any other nationally recognized testing laboratory and be used for the certified purposes only. The installation shall be performed by a licensed heating contractor, and it shall be the responsibility of the installing contractor to make the installation according to the manufacturer's instructions.
(Sec. 30.25(5) Am. by Ord. 6576, 3-21-79)
Ask a question about Madison law
Corpus searches the Madison sections it holds and shows the ones that match, with their citations. Free, no sign-in.