SEC. 11-724. - PRESSURIZATION OF EXIT STAIRWAY ENCLOSURE.
If pressurization of exit stairway enclosure is required, then a mechanical ventilation system shall be provided. The mechanical ventilation system shall provide a uniform air velocity of not less than 50 feet per minute while maintaining a positive pressure (not exceeding 25 pounds force on an interior door) relative to the adjacent areas and discharging this air to the outside of the building. The mechanical ventilation system shall be activated simultaneously with the fire sprinkler system or the smoke detector system. The mechanical ventilation system shall be supplied with primary and secondary sources of power. The primary power shall be provided by the power system supplied by the public utilities. The secondary power shall be from an approved standby source complying with the Electrical Code.
(Added Ord. 2007-102, § 1, eff. 1-20-08).