§ 30.21 — VENTING REQUIREMENTS
Madison General Ordinances (Rev. 28, Update 3: codified through ORD-26-00040, published August 3, 2026) · Madison General Ordinances § 30.21
Corpus is an independent public-information project, not the official City of Madison website. Stable reference: corpuslaw.us/code/6ca55b65-2f02-4424-89ed-aec6411567d6
30.21 - VENTING REQUIREMENTS.
(1) General. The venting of all boilers, furnaces or appliances shall conform to the requirements as hereinafter set forth inclusive of this section, together with their subdivisions. Conditions not specifically mentioned in this section shall be governed by the current A.S.H.R.A.E. Guides or Section V of the standards of the National Fire Protection Association for the installation of gas appliances and gas piping. N.F.P.A. 54 as listed in Appendix No. 1. (2) Types of Chimneys or Vents Defined. For the purpose of this section, the following definitions shall govern as to the meaning of the several terms or expressions herein defined, whenever said terms and expressions are employed in this code. (a) Chimneys. 1. Factory Built Chimneys. Chimneys that are factory made, listed by a nationally recognized testing agency, for venting gas appliances, gas incinerators, and solid or liquid fuel burning appliances. 2. Masonry Chimneys. Field constructed chimneys built in accordance with the City of Madison Building Code (Chapter 29). 3. Metal Chimneys. Chimneys made of metal of adequate thickness properly galvanized or properly welded or riveted and built in accordance with nationally recognized codes or standards. (b) Gas Vents. 1. Type B Gas Vents. Factory made gas vents listed by a nationally recognized testing agency for venting listed or approved appliances equipped to burn only gas. 2. Type B/W Gas Vents. Factory made gas vents listed by a nationally recognized testing agency for venting listed or approved gas-fired recessed heaters. 3. Type C Gas Vents. Vents constructed of sheet copper not less than twenty-four (24) ounces per square foot or galvanized iron of not less than No. 20 U. S. Standard gauge or other approved noncombustible corrosion-resistant material. (c) Chimney Liner. A vent pipe or flue liner inserted within a chimney for the purpose of flue products and preventing such condensation from contact with the interior of the chimney in which it is inserted. (d) Chimney Flue. The flue gas conveying passageway in a chimney. (e) Vent. A conduit or passageway, vertical or nearly so, for conveying vent gases to the outer air. (f) Chimney Connector. (Use in place of smoke pipe or flue pipe.) The pipe which connects a solid or liquid fuel burning appliance to a chimney. (g) Vent Connector. The pipe which connects a gas appliance to a gas vent or chimney. (h) Draft Hood. A device built into an appliance, or made a part of the vent connector from an appliance which is designed to (1) assure the ready escape of the flue gases in the event of no draft, back draft, or stoppage beyond the draft hood; (2) prevent a back draft from entering the appliance; and (3) neutralize the effect of stack action of the chimney or gas vent upon the operation of the appliance. (3) Draft Hoods; Use of. (See Section 30.25) (4) Barometric Dampers. Barometric dampers shall be constructed and installed in accordance with the manufacturer's instructions. (5) Types of Chimneys or Vents, Use of. It shall be the duty of the owner of any building in which it is hereafter proposed to install any furnace, boiler or appliance to provide a properly constructed chimney or vent. (a) Gas vents or chimney systems shall be engineered and constructed so as to develop a positive flow adequate to remove all flue gases to the outside atmosphere. (b) Chimneys. Chimneys shall be used for venting the following types of appliances. 1. Incinerators, except that metal pipe not less than No. 20 U.S. Standard gauge galvanized iron or other equivalent noncombustible, corrosion-resistant material may be used for venting incinerators installed in locations such as open sheds, breezeways or carports, provided the metal pipe is exposed and readily examinable for its full length and suitable clearance (eighteen inches from combustible) are maintained. 2. Appliances which may be converted readily to the use of solid or liquid fuels. 3. Combination gas-oil burning appliances. 4. Appliances listed for use with chimneys only. (c) Type B Gas Vents. 1. Type B gas vents may be used to vent listed gas appliances except as provided in 30.21(5)(b) and (d) and 30.21(7)(a). 2. For the purpose of this section, listed gas appliances shall refer to appliances which are shown in a list published by an approved, nationally recognized testing agency, qualified and equipped for experimental testing and maintaining an adequate periodic inspection of current production of listed models and whose listing states either that the appliance complies with nationally recognized safety requirements or has been tested and found safe for use in a specific manner. Listed gas appliances are considered to be equipped with draft hoods and to produce flue gas temperatures not in excess of five hundred fifty (550) degrees Fahrenheit at the outlet of the draft hood when operating at the manufacturer's normal input rating. 3. Listed Type B vents shall be installed in accordance with their listings and the manufacturer's instructions. 4. Type B vents installed outside a building, or which pass through unheated portions of a building except that portion above the roof line, shall be equipped with a capped tee with provision for a condensate drain, so arranged that excessive condensation may be disposed of without damage to the foundation, floor, walls or footings. 5. Any shape listed gas vent may be used provided its venting capacity is equal to the capacity of round pipe for which it is substituted and the minimum internal dimension of the gas vent is not less than two (2) inches. 6. The gas vent or chimney should extend high enough above the building or other neighboring obstruction so that wind from any direction will not create a positive pressure in the vicinity of the gas vent or chimney termination. Gas vents shall extend at least two (2) feet above the highest point where they pass through a roof or a building and at least two (2) feet higher than any portion of a building with ten (10) feet except that gas vents need not comply with this provision when equipped with an approved device and proper and effective venting is accomplished. Gas vents or chimneys shall not terminate less than four (4) feet in vertical height above the highest connected appliance draft hood outlet or flue collar. 7. Gas vents and factory built chimneys shall extend above the roof surface and through the flashing and shall terminate in a top or listed room assembly with a venting capacity not less than that of the gas vent or chimney. The top shall be of a design to prevent rain and debris from entering the gas vent or chimney. 8. All portions of gas vents and chimneys shall be adequately supported for the weight and design of the materials employed. Listed gas vents and factory built chimneys shall be supported and spaced in accordance with their listings and the manufacturer's instructions. 9. Size of Gas Vent or Chimney. The gas vent or chimney, when connected to a single appliance, shall be not less than the size of the draft hood outlet, or as provided in Section 30.21. When more than one (1) appliance is connected to a gas vent or chimney, the area of the passageway shall be not less than the area of the largest vent connector, plus fifty percent (50%) of the areas of additional vent connectors or as provided in Subsection (8) hereof. (d) Marking of Type B Vents. Gas vent systems shall be plainly and permanently identified by a label reading: "This gas vent is for appliances which burn gas only. Do not connect to incinerators or solid or liquid fuel burning appliances." This label shall be attached to the wall or ceiling at a point near where the gas vent system enters the wall, ceiling or chimney. (e) Type BW Gas Vents. 1. Type BW gas vents shall be used with listed vented recessed heaters when installed with combustible two by four (2 x 4) wall construction. 2. Listed Type BW gas vents shall be installed in accordance with their listings and the manufacturer's instructions. 3. Type BW gas vents serving a vented recessed heater shall not terminate less than twelve (12) feet in vertical height above the bottom of the heater. 4. Type C Gas Vents. a. Type C gas vents shall be used only for runs directly from the space in which the appliance is located through the roof to the outer air. Such gas vents shall not originate in any unoccupied attic or concealed space, and shall not pass through any attic, inside wall, concealed space, or through any floor. b. When a Type C gas vent passes through a roof constructed of combustible material, it shall be guarded at the point of passage by a method described in 30.21(6)(n) or by a noncombustible nonventilating thimble not less than four (4) inches larger in diameter than the vent pipe and extending not less than eighteen (18) inches above and six (6) inches below the roof with annular space open at the bottom and closed only at the top. (6) Vent Connectors. (a) Materials. Vent connectors used for gas appliances having draft hoods and for listed conversion burners having draft hoods, shall be constructed of materials having resistance to corrosion and heat not less than that of No. 24 U.S. Standard gauge galvanized steel except that Type B vent material may be used as the connector between the draft hood and the chimney. (b) Clearance. Vent connectors shall be located in such a manner that continued operation of the appliance will not raise the temperature of surrounding combustible construction more than ninety (90) degrees Fahrenheit above normal room temperature when measured with mercury thermometers or conventional bead type thermocouples. Minimum clearances of vent connectors to combustible material shall be in accordance with Table No. 1 of this section. (c) Avoid Unnecessary Bends. The vent connector shall be installed so as to avoid excessive turns or other construction features which create unnecessary resistance to flow of vent gases. (d) Joints. Vent connectors shall be firmly attached to draft hood outlets by sheet metal screws or other approved means. Vent connectors using listed Type B gas vent material shall be securely assembled, using the method shown in the listing and the manufacturer's instructions. Joints of other than listed Type B gas vent material shall be securely fastened by sheet metal screws or other approved materials. (e) Pitch. Vent connectors attached directly to side outlet draft hoods, such as on floor furnaces, shall be pitched upward from the appliance at least one-fourth (¼) inch per foot. Vent connectors attached to top outlet draft hoods by means of a ninety (90) degree elbow may be horizontal or pitched upward from the appliance. No portion of any vent connector shall be run downward from the appliance nor shall there be any dips or sags. (f) Length. The horizontal run of the vent connector shall be as short as possible and the appliance shall be located as near to the gas vent or chimney as practicable. The maximum length of an uninsulated horizontal run of vent connector shall not exceed seventy-five percent (75%) of the height of the gas vent or chimney. TABLE NO. 1 VENT CONNECTOR CLEARANCES FOR GAS APPLIANCES Appliance | Minimum Distance from Combustible Material Listed Type B Gas Vent Material | Vent Connectors of Other than Type B Material Listed Boiler | 1" or as listed* | 6" Listed Warm Air Furnace | 1" or as listed* | 6" Listed Water Heater | 1" or as listed* | 6" Listed Room Heater | 1" or as listed* | 6" Listed Floor Furnace | 1" or as listed* | 6" Listed Incinerator | Not Permitted | 18" Listed Conversion Burner (with draft hood) | 6" | 9" Unlisted Appliances (having draft hoods) | 6" | 9" Unlisted Appliances (without draft hoods) | Not Permitted | 18" *Where listing by national agency calls for greater distance, that distance shall apply. The clearances from vent connectors to combustible materials may be reduced when combustible material is protected as specified in Table No. 2. TABLE NO. 2 REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION Type of protection applied to & covering all surfaces of combustible material w/in distance specified as required clearance w/no protection (See Figs. 7,8,9) | Where required clearance w/no protection from appliance, vent connector, or single wall metal pipe is: 36" | 18" | 12" | 9" | 6" Allowable Clearances w/Specified Protection, inches Above | Sides and Rear | Above | Sides and Rear | Above | Sides and Rear | Above | Sides and Rear | Above | Sides and Rear a) 3½" thick masonry wall w/out ventilated air space | — | 24 | — | 12 | — | 9 | — | 5 | — | 5 b) ½" insulation board over 1" glass fiber or mineral wool batts | 24 | 18 | 12 | 9 | 9 | 6 | 6 | 5 | 4 | 3 c) 0.024 (24 gauge) sheet metal over 1" glass fiber or mineral wool batts reinforced w/wire on rear face w/ventilated air space | 18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 d) 3½" thick masonry wall w/ventilated air space | — | 12 | — | 6 | — | 6 | — | 6 | — | 6 e) 0.024 (24 gauge) sheet metal w/ventilated air space | 18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 2 f) ½" thick insulation board w/ventilated air space | 18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 g) 0.024 (24 gauge) sheet metal w/ventilated air space over 0.024 (24 gauge) sheet metal w/ventilated air space | 18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 h) 1" glass fiber or mineral wool batts sandwiched between two sheets 0.024 (24 gauge) sheet metal w/ventilated air space | 18 | 12 | 9 | 6 | 6 | 4 | 5 | 3 | 3 | 3 NOTES APPLICABLE TO TABLE NO. 2 1. Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing. 2. All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding any intervening protection applied to the combustible material. 3. Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite appliance or connector. 4. With all clearance reduction systems using a ventilated air space, adequate provision for air circulation shall be provided as described. (See Figures 7 and 8.) 5. There shall be at least 1 inch between clearance reduction system and combustible walls and ceilings for reduction systems using ventilated air space. 6. If a wall protector is mounted on a single flat wall away from corners, adequate air circulation may be provided by leaving only the bottom and top edges or only the side and top edges open with at least 1 inch air gap. 7. Mineral wool batts (blanket or board) shall have a minimum density of 8 lb/ft3 and a minimum melting point of 1500°F. 8. Insulation material used as part of clearance reduction system shall have a thermal conductivity of 1.0 (Btu-in)/(sq ft-hr-F) or less. 9. There shall be at least 1 inch between the appliance and the protector. In no case shall the clearance between the appliance and the combustible surface be reduced below that allowed in the table. 10. All clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable. (g) Support. Vent connectors shall be securely supported for the weight and design of the materials employed to maintain proper clearances to prevent physical damage and to prevent separation of the joints. Support shall be accomplished by means of metal hangers spaced not more than six (6) feet on centers. Wire hangers will not be permitted. (h) Provide Vertical Run. Vent connectors shall have the greatest possible rise consistent with head room available between the draft hood outlet and the start of the horizontal run. (i) Location. When the vent connector used for an appliance having a draft hood must be located in, or pass through a crawl space or other area difficult of access which may be cold, that portion of the vent connector shall be of listed Type B gas vent material or material having equivalent insulation qualities. Type C gas vent material used as a vent connector shall not pass through any floor or ceiling. (j) Chimney Connection. When an existing chimney wall is to be pierced for a chimney connection, approval shall be obtained from the Building Inspection Division of the Department of Planning and Community and Economic Development before the opening is cut. An inspection shall be made and approved before the connection is made to the opening. In entering a passageway in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Means shall be employed which will prevent the vent connector from entering so far as to restrict the space between its end and the opposite wall of the chimney. A thimble or slip joint may be used to facilitate removal of the vent connector. The vent connector shall be firmly attached or inserted into the thimble or slip joint to prevent it from falling out. (Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (k) Fireplace. A vent connector shall not be connected to a chimney serving a fireplace unless the fireplace opening is permanently sealed. (l) Size, Height and Length of Interconnected Vent Connectors. Two (2) or more vent connectors may be joined through a gas vent manifold or to a gas vent provided that: 1. Vent connectors carrying the gases of a single appliance shall have the greatest possible rise consistent with the head room available between the draft hood outlet and the points of its interconnection to manifold or to common vent. 2. Size of vent connector shall be equal to or greater than the size shown in Table No. 3 of this section for the allowable heat input. 3. When Table No. 3 indicates that a vent connector must have a larger size than the draft hood, the size increase shall be made at the draft hood outlet. TABLE NO. 3 ALLOWABLE INPUT TO VENT CONNECTORS BEFORE INTERCONNECTION Connector Size in Inches | Maximum Appliance Input — In BTU Per Hour 3 | 30,000 4 | 55,000 5 | 80,000 6 | 125,000 7 | 180,000 8 | 245,000 9 and above | 5,000 BTU per square inch of cross-sectional area. (m) Dampers. Manually operated dampers shall not be placed in the vent connector from any gas appliance except an incinerator. Fixed baffles ahead of draft hoods are not classified as dampers. (n) Use of Thimbles. 1. When passing through combustible walls or partitions, vent connectors built of listed Type B gas vent material shall be installed so that the clearances required by the listing are maintained. 2. Vent connectors made of other than Type B vent material shall not pass through any combustible walls unless they are guarded at the point of passage by ventilated thimbles not smaller than the following: For listed appliances, except incinerators - four (4) inches larger in diameter than the vent connector, unless there is a run of not less than six (6) feet of vent connector in the open, between the draft hood outlet and the thimble in which case the thimble may be two (2) inches larger in diameter than the vent connector. For unlisted appliances having draft hoods - six (6) inches larger in diameter than the vent connector. For incinerators and unlisted appliances - twelve (12) inches larger in diameter than the vent connector. 3. In lieu of thimble protection, all combustible material in the wall shall be cut away from the vent connector a sufficient distance to provide the clearance required from such vent connector to combustible material. Any material used to close up such opening shall be noncombustible. (o) Size. Vent connectors shall not be smaller than the size of the flue collar or the draft hood outlet. When the appliance has more than one (1) draft hood outlet and in the absence of the appliance manufacturer's specific instructions, the vent connector shall equal the combined area of the draft hood outlets for which it acts as a common connector to the gas vent chimney. (7) Special Venting Arrangements. (a) Appliances With Sealed Combustion Chamber. The provisions of draft hoods in Section 30.21 (1) through (6), do not apply to listed appliances having sealed combustion chambers and which are so constructed and installed that all air for combustion is derived from outside the space being heated and all flue gases are discharged to the outside atmosphere. Such appliances, having integral venting, shall be considered as being properly vented when they are installed in accordance with their listing and the manufacturer's instructions. (b) Gas Vent and Chimney Exhausters. Forced venting and exhaust systems and power burners usually require special engineering and shall, in all cases, be subject to the approval of the Director of the Building Inspection Division. However, when used, the following regulations shall apply: 1. When an exhauster is used with gas appliances requiring venting, provisions shall be made to prevent the flow of gas to the main burner in the event of failure of the exhaust system. 2. A vent connector serving a gas appliance vented by natural draft shall not be connected into the discharge side of a power exhauster. 3. Induced Draft. Where an induced draft or forced draft fan is used with gas, oil or solid fuel, it shall be equipped with a control that will not allow burner to start until proper draft has been established. (8) Engineered Vent Systems. The size of chimneys, gas vents or vent connectors specified in this section shall not necessarily govern where standard engineering methods have been used to design the vent system. (9) Flues or Vents. This section applies only to natural draft venting. Forced venting or exhaust systems and power burners usually require special engineering and shall, in all cases, be subject to the approval of the Director of the Building Inspection Division. (Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (a) Check Flue or Vent. Before connecting a flue or vent connector, the flue or vent shall be examined to ascertain that it is properly constructed, clear, and will freely conduct the products of combustion to the outer air. (b) Size. For conversion burners not exceeding four hundred thousand (400,000) hourly BTU input, the internal cross-sectional area of the vent connector and the vent flue shall be such as to provide not less than one (1) square inch of flue area per six thousand five hundred (6,500) BTU combined input of all gas appliances connected to such flue pipe as set forth in Table No. 3. In no case shall this flue pipe be less than five (5) inches in diameter. For conversion burners exceeding four hundred thousand (400,000) hourly BTU input, where the chimney or vertical flue is of such height as to provide a high draft intensity, the area of the chimney or vertical flue may be based on an input of greater than six thousand five hundred (6,500) BTU per square inch of cross-sectional area, subject to the approval of the Building Inspection Division of the Department of Planning and Community and Economic Development. (Am. by ORD-08-00109, 10-7-08) TABLE NO. 4 MINIMUM PERMISSIBLE FLUE SIZES FOR GAS CONVERSION BURNER INSTALLATIONS Input Rating BTU Per Hour | Area of Flue Outlet - Sq. In. | Diameter of Flue Pipe - Inches 120,000 | 19.6 | 5 160,000 | 28.3 | 6 250,000 | 38.5 | 7 320,000 | 50.3 | 8 410,000 | 63.6 | 9 (10) Insufficient Draft or Down-Draft to be Provided Against. In the event conditions at the time of installation are such that the chimney or vertical flue has insufficient natural draft to properly carry away the products of combustion, provision shall be made to rectify existing conditions or provide mechanical means of maintaining constant up-drafting during appliance operation. The draft must be proved before the burner may be operated. (11) Smoke Pipes. (a) Required Weight of Metal Smoke Pipes Used With Solid and Liquid Fuels. For each and every steam or hot water boiler, warm air furnace or incinerators hereafter installed under the provisions of this code, the area of the breeching or smoke pipe shall not be less than the area of the smoke collar of the boiler or furnace to which it is connected, and each such breeching or smoke pipe shall be made of material equal in durability to galvanized iron of thicknesses (U.S. Standard Gauge), for the various breeching or smoke pipes, not less than the following: For areas from 13 to 113 square inches - No. 24 Gauge. For areas from 114 to 177 square inches - No. 18 Gauge. For areas from 178 to 314 square inches - No. 16 Gauge. For areas from 315 to 616 square inches - No. 14 Gauge. For areas from 617 to 1,017 square inches - No. 12 Gauge. For areas from 1,018 to 2,827 square inches - No. 10 Gauge. (b) Smoke Pipes, How Installed. Each such breeching or vent connector or smoke pipe shall be lock seamed or riveted, with all joints lapped not less than one and one-half (1½) inches or be rigidly secured, and shall have proper construction for making tight connection to chimney flue the full thickness of masonry, and shall not extend more than one-fourth (¼) inch beyond liner. The smoke pipe shall extend full size of the chimney flue for not less than one and one-half (1½) diameters nor more than two (2) diameters so that additional appliances may be properly vented into the manifold. Smoke pipes shall be supported by means of strap hangers spaced not less than six (6) feet on centers. Wire hangers will not be permitted. Each such breeching or smoke pipe shall be as short and direct to the chimney flue as possible, and shall be installed with a pitch upward of not less than one-fourth (¼) inch per running foot. (c) Multiple Smoke Pipe Connections. Two (2) or more smoke pipes shall not be jointed for a single flue connection unless the smoke pipe and flue are of sufficient size to serve all the appliances so connected. The manifold for multiple smoke pipe connections shall be designed and installed so that the inlet connections enter so as not to cause opposed venting. (d) Clearances. No part of any smoke pipe shall be placed nearer to any combustible ceiling than one and one-half (1½) times the diameter of the pipe; or nearer to any combustible wall than one (1) diameter of the pipe; but the above distances may be reduced by one-half (½) if the wall or ceiling is covered with one-fourth (¼) inch asbestos paper and a metal shield so fastened so that an inch space exists between this shield and the combustible material. (12) Dampers. All smoke pipes on hand-fired coal equipment shall be provided with a check damper placed on the side of the smoke pipe or at the end of a tee. Where cast iron smoke pipe dampers are used, they must be placed between the check damper and the heating equipment and supported on both sides of pipe. The smoke pipe on all incinerators that are not fired by auxiliary fuel shall have a cast iron damper to control the draft. Automatically operated dampers shall be of approved type designed to maintain a safe damper opening at all times and arranged to prevent starting of the burner unless the damper is opened, at least twenty percent (20%) of the internal cross-section area. (13) Draft Regulators. A draft regulator or draft hood shall be provided for all fired appliances, unless the burner is listed for use without one. (Refer to Section 30.25.)
(Sec. 30.21(6)(f)Table 2 R. & Re-Cr. by Ord. 10,255, Adopted 5-7-91) (Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (Sec. 30.21(9) (Am. by Ord. 8081, 7-29-83)
Ask a question about Madison law
Corpus searches the Madison sections it holds and shows the ones that match, with their citations. Free, no sign-in.