18-28-1107.7 Stop valves.

All systems containing more than 6.6 pounds (3 kg) of a refrigerant in systems using positive-displacement compressors, shall have stop valves installed at the inlet of each compressor, compressor unit or condensing unit. Exceptions: 1. Systems that have a refrigerant pump out function capable of storing the entire refrigerant charge in a receiver or heat exchanger. 2. Systems that are equipped with provisions for pump out of the refrigerant using either portable or permanently installed recovery equipment. 3. Self-contained systems.