§ 8-563 — Duct testing criteria
The Little Rock City Code, Revised 1988 (Supp. No. 83: codified through Ordinance No. 22,703, enacted December 16, 2025) · Little Rock City Code § 8-563
Corpus is an independent public-information project, not the official City of Little Rock website. Stable reference: corpuslaw.us/code/7a3ca9cd-85c9-42c7-8211-1581f0bbb24d
Sec. 8-563. - Duct testing criteria.
Duct testing shall be verified by either of the following: (1) Rough-in test. Total leakage shall be less than or equal to six (6) cfm (169.9L/min) per one hundred (100) feet 2 (9.29m 2 ) of conditioned floor area when tested at a pressure differential of one-tenth (0.1) inches w.g. (25 Pa) across the roughed in system, including the manufacturer's air handler enclosure. All register boots shall be taped or otherwise sealed during the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to four (4) cfm (113.L/min) per one hundred (100) feet 2 (9.29m 2 ) of conditioned floor area. (2) Post construction test. Leakage to outdoors shall be less than or equal to eight (8) cfm (226.5 L/min) per one hundred (100) feet 2 (9.29m 2 ) of conditioned floor area or a total leakage less than or equal to twelve (12) cfm (12 L/min) per one hundred (100) feet 2 (9.29m 2 ) of conditioned floor area when tested at a pressure differential of one-tenth (0.1) inches w.g. (25Pa) across the entire system, including the manufacturer's air handler enclosure. All register boots shall be taped or otherwise sealed during the test. Exceptions: Duct tightness test is not required if the air handler and all ducts are located within conditioned space. (3) Duct testing compliance and verification. The tester shall provide (city-provided form) within five (5) days of completion to the building codes division, the results of the test and that the duct testing complies with subsection 8-563(1) or subsection 8-563(2). A certificate of occupancy shall not be issued without completion verification and compliance with the duct testing requirements. (4) Sticker. The 2014 AR Energy Code label shall be completed and posted permanently on the electrical distribution panel and front entrance of structure. The sticker may be removed from the front entrance after occupancy or sale of the property. Under other information the date of duct testing shall be noted.
(Ord. No. 21,577, § 1, 4-3-18)
Ask a question about Little Rock law
Corpus searches the Little Rock sections it holds and shows the ones that match, with their citations. Free, no sign-in.