§ 11-718 — FIRE PUMPS AND GENERATOR (COMBUSTION ENGINES AND GAS TURBINES) ROOMS
Fresno Municipal Code (Supp. No. 55, Update 1 (online June 23, 2026): codified through Ordinance No. 2026-019) · Fresno Municipal Code § 11-718
Corpus is an independent public-information project, not the official City of Fresno website. Stable reference: corpuslaw.us/code/84613a33-8706-4148-9012-fdf99d5de189
SEC. 11-718. - FIRE PUMPS AND GENERATOR (COMBUSTION ENGINES AND GAS TURBINES) ROOMS.
In high-rise buildings, diesel or/and electric fire pumps shall be provided as required for a new building. Fire pump and generator (combustion engines and gas turbines) rooms shall be separated with a minimum one-hour occupancy separation from adjoining rooms and from each other. Combustion air and room ventilation air shall be required by the Building and Mechanical Codes, except that the room ventilation exhaust may be considered as environmental air.
(Added Ord. 2007-102, § 1, eff. 1-20-08).
Ask a question about Fresno law
Corpus searches the Fresno sections it holds and shows the ones that match, with their citations. Free, no sign-in.
