30.26 - COMMERCIAL AND INDUSTRIAL BURNERS OVER TEN (10) GALLONS PER HOUR OR 1,500,000 BTU PER HOUR.
(1) General. Flame safeguard equipment on all gas and/or oil burning equipment shall be two (2) wire, one hundred twenty (120) volt, one side grounded and approved for the equipment it is to be installed with. On commercial gas or combination gas-oil burners, a hi-lo gas pressure switch shall be provided and wired so that the main fuel valve cannot open if the gas pressure is above or below the rating of the equipment. On pressure type burners, forced draft burners or induced draft burners, an air flow switch shall be provided so that the main fuel valve cannot open unless all fans are running. Natural draft burners must have a prepurge period of a minimum of ninety (90) seconds after the burner motor starts and all dampers are wide open before opening the fuel valve. Forced or induced draft burners must have a prepurge period of at least four (4) air changes after the motor starts and all dampers are wide open before opening the fuel valve. Oil burners shall be equipped with low fire start. Gas burners shall be equipped with slow opening gas valves. Where gas pressures exceed fourteen (14) inches W.C. piped to a burner, an applicable gas pressure regulator shall be installed at each burner. The automatic gas valve shall be slow opening motorized with positive shutoff in case of power failure. (2) Continuous Pilot Burning. Gas burners using continuous pilots shall be equipped with U.L. or A.C.A. approved safety pilot and automatic shutoff valve. (3) Location of Pilot Valves. The gas supply to the pilot or group of pilots on all burners shall be controlled independently of the main gas burner including independent manual shutoff valve.
Ask a question about Madison law
Corpus searches the Madison sections it holds and shows the ones that match, with their citations. Free, no sign-in.