30.14 - STEAM AND HOT WATER HEATING SYSTEMS.
(1) Definitions. For the purpose of Section 30.14, the following definitions shall govern as to the meaning of the several terms and expressions therein defined, wherever said terms and expressions are employed in this Code. (a) A gravity system is one in which the condensate is returned to the boiler by gravity due to the static heat of water in the return mains. The elevation of the boiler water line must consequently be sufficiently below the lowest heating units and steam main and dry return mains to permit the return to condensate by gravity. The water line difference must be sufficient to overcome the maximum pressure drop in the system and when radiator and drip traps are used as in two-pipe vapor systems, the operating pressure of the boiler. This applies only to closed circuit systems where the condensation is returned to the boiler. If the condensation is wasted, no water line difference is required. (b) A mechanical return system is one in which the condensate flows to a receiver and is then forced into the boiler against the boiler pressure. The lowest parts of the supply side of the system must be kept sufficiently above the water line of the receiver to insure adequate drainage of water from the system, but the relative elevation of the boiler line is unimportant in such cases except that the discharge head on the mechanical return device becomes greater as the height of the boiler water line above the pump increases. There are three (3) general types of mechanical returns in common use, namely: 1. The mechanical return trap, 2. The condensation return pump, and 3. The vacuum return pump. (c) Service Mains. 1. Supply service mains shall be defined as those pipes through which the steam flows from the boiler or pressure reducing valve and to which the radiator supply branches are connected. 2. Return service mains shall be defined as those pipes which carry condensate to the boiler or mechanical return device, and to which the radiator return branches are connected. (d) Down-feed or overhead systems shall be defined as those in which the supply mains are above the level of the radiation which they serve. (e) Up-feed systems shall be defined as those in which the supply mains are below the level of the radiation which they serve. (f) One-pipe systems shall be defined as those in which the steam supply to the radiation and the return of condensation flow are in opposition to each other. (g) Two-Pipe systems shall be defined as those in which one pipe is used for the supply of steam to the radiator and another for the return of condensation. (h) Dry returns shall be defined as those returns through which both water and air are being passed. (i) Wet returns shall be defined as those returns through which water only is being passed. (j) Vacuum returns shall be defined as those returns through which both water and air are being passed and upon which a vacuum is maintained at all times through the medium of a vacuum producer. (k) Equivalent length of run shall be defined as the actual distance in feet from source of steam supply, boiler or pressure reducing valve, to the farthest radiator in system, and then back along return line to boiler or mechanical return device, plus resistance of all fittings and valves as expressed in terms of straight pipe. (l) Transmission mains shall be defined as those pipes which though not actually a part of the heating system proper, are connected to the service mains of the system and act as sources of supply to same. (m) Gravity Hot Water Systems. Gravity hot water heating systems shall be defined as those in which the water is circulated through the radiation and connecting piping by virtue of the difference in density of the water in the flow and return risers. (n) Forced Hot Water Systems. Forced hot water heating systems shall be defined as those in which the water is circulated through the radiation and connection piping principally by means of a pump. (o) Open Gravity Systems. Open gravity hot water heating systems shall be defined as those in which expansion tanks are used, installed above the level of the highest radiator of the system which they serve and vented directly to the atmosphere. (p) Closed Gravity Systems. Closed gravity hot water heating systems shall be defined as those in which some device enables the system to be operated at a pressure in excess of the pressure corresponding to the static head of the system. (q) Supply or Flow Mains. The supply or flow mains of a hot water heating system shall be defined as those pipes through which the water flows from the boiler and to which the radiator supply branches are connected. (r) Return Mains. The return mains of a hot water heating system shall be defined as those pipes through which the water flows on its return to the boiler and to which the radiator return branches are connected. (2) Steam. Minimum Requirements for Determining Amount of Direct Steam Radiation to be Installed. (a) The amount of equivalent direct radiation to be installed in a given room where unenclosed radiators are to be employed shall be determined by dividing the heat loss of the room in BTU per hour by two hundred forty (240). (b) Convectors and Baseboard Used on Steam. All convectors used with steam as the heating medium shall be piped as a two-pipe system unless the convector is specifically designed for use on a one-pipe system. All baseboard radiation shall be piped as a two-pipe system and shall be installed according to the manufacturer's recommendations. (c) Enclosed Radiators. If cast iron direct radiators are to be recessed or enclosed in a cabinet, proper allowance shall be made for capacity loss or gain incurred by this type of installation. (d) Selection of convectors and baseboard ratings used in selecting convectors and baseboards shall be those as published by the Mechanical Contractor's Association of America, or any other nationally recognized rating authority. (3) Hot Water. Minimum Requirements for Determining Amount of Direct Hot Water Radiation to be Installed. (a) The amount of equivalent direction radiation to be installed in a given room where unenclosed radiators are to be employed shall be determined by dividing the heat loss of the room in BTU per hour by the BTU heat emission of the radiation at the design average water temperature as given by the manufacturer of the radiation. (b) Design Water Temperature. 1. Gravity Hot Water. Gravity hot water systems shall be designed on the basis of one hundred seventy (170) degrees average water temperature. Only radiation designed for gravity hot water shall be used. 2. Forced Hot Water. The average water temperature to be used in designing forced hot water systems shall not be higher than one hundred eighty (180) degrees average hot water temperature. (4) Minimum Capacity and Installation Requirements for Low Pressure System and Hot Water Boilers; Ratings for Such Boilers, How Determined; High Pressure Source of Steam Supply. The manner of installation of all low pressure steam and hot water boilers hereafter installed for use in connection with heating systems, the minimum required capacities thereof and the ratings to be assigned thereto shall conform to the following provisions. (a) Boiler Foundation. 1. Each steam or hot water boiler hereafter installed in any basement for use in connection with space heating plants shall be supported on a level concrete foundation. Where installed on any floor above the basement, each such boiler shall rest upon concrete or other fireproof floor, construction having no wooden or other combustible finish. Provided, however, that where any such boiler is to be installed on any floor above the basement in any building constructed prior to the passage of this Ordinance, the method of supporting such boiler, both as to fireproofing and construction, shall be subject to the approval of the Building Inspection Division of the Department of Planning and Community and Economic Development. 2. Boiler Capacity to be Installed. All boilers not rated by a recognized testing laboratory shall have a net rating equal to sixty percent (60%) of fuel input. Note: The Building Inspection Division of the Department of Planning and Community and Economic Development accepts net ratings as listed by Mechanical Contractor's Association of America, Inc., Steel Boiler Institute, Inc., Institute of Boiler and Radiator Manufacturers, and American Gas Association. 3. It shall be unlawful for any person, firm, corporation, or their agent, to sell or install any boiler for use in the City of Madison that has not been rated by any of the above-mentioned organizations until the boiler has been approved by the Building Inspection Division of the Department of Planning and Community and Economic Development. The application for approval shall include name of boiler, manufacturer's name, complete literature giving all physical dimensions and manufacturer's recommended net load. (b) Steam Supply, Where Taken From High Pressure Boilers. In every case where steam supply for a low pressure heating plant is taken from a high pressure boiler or boilers from which steam may or may not be furnished for other purposes, the capacity of such boiler or boilers shall be adequate to meet the demand to be placed upon them under peak load conditions, and a proper reducing valve or valves, with bypasses, capable of maintaining a reduced pressure of not to exceed fifteen (15) pounds per square inch on the heating system shall be installed between said high pressure boiler or boilers and the heating system. A relief valve of proper capacity set at not to exceed fifteen (15) pounds per square inch shall be installed on the low pressure side. (5) Minimum Requirements for Pipe Sizes of Low Pressure Steam Vapor and Vacuum Heating Systems. (a) Pipe sizes of all low pressure steam, vapor and vacuum heating systems shall be as hereinafter provided for in this section of this code. (b) Service Main Design. All supply and return mains in heating systems shall be designed for a low initial pressure and a reasonable small pressure drop. The total pressure drop shall never exceed one-half (½) of the initial pressure when condensate is flowing in the same direction as the steam. Where condensate must flow counter to the steam, the governing factor is the velocity permissible without interfering with condensate flow. Capacity Tables as shown in the American Society of Heating, Refrigeration and Air Conditioning Engineers' Guide, as listed in Appendix No. 1, shall be used when designing steam supply and return mains. It shall be noted that these tables show the capacity of pipe per one hundred (100) feet of equivalent length of run. In using these tables allowance shall be made for fittings and length of run. All steam supply and return mains shall be pitched not less than one-fourth (¼) inches in ten (10) feet. (c) Steam Riser and Runout Design. The size of all risers and runouts shall be taken from the tables in the American Society of Heating, Refrigeration and Air Conditioning Engineers' Guide, or Part 3, Pipe Sizes and Design of Heating, Piping and Air Conditioning of the Contractors' National Association as per Appendix No. 1. Radiator runouts over eight (8) feet long shall be increased one pipe size. Pitch of horizontal runouts to risers and radiators shall be not less than one-half (½) inch in ten (10) feet. Supply mains, branches to risers or risers, shall be dripped where necessary. Where necessary, supply main, supply riser, or branches to supply riser should be dripped separately into a wet return. (6) Piping and Piping Connections and Equipment for Low Pressure Steam, Vapor and Vacuum Heating Systems and Hot Water Systems. (a) Piping and piping connections and equipment hereafter installed for all steam and hot water heating plant installations, or portions of such installations, shall conform to the following requirements: 1. Pipe. All pipe used shall be not less in weight and strength than that known to the trade as "Standard Wrought Pipe". Provided, however, that brass pipe and copper tubing may be so used where desired, the weight of all such pipe and tubing to be subject to the approval of the Building Inspection Division of the Department of Planning and Community and Economic Development. The weight of all such pipe and tubing to be Type M or heavier for aboveground and Type L or heavier for underground. No pipe or tubing shall be so used that is not in sound condition. 2. Reaming. All pipe, after cutting shall be reamed to full internal diameter. 3. Fittings and Joints. Piping may be joined together by welding or by the use of fittings. Such welds shall be made in a neat workmanlike manner and shall be as strong as base metal. Fittings shall be of cast or malleable iron or of brass, and of standard weight, and clean-cut threads and free from blow-holes or other defects. 4. Expansion and Contraction, Allowance For. In all piping systems which are subject to expansion and contraction, provision shall be made for adequate anchorage and protection against damage to piping from such expansion and contraction. All risers shall be so anchored and safeguarded that the difference in length, when hot, from the length when cold, shall not disarrange the necessary provisions for drainage of the branches or distort, damage or displace radiators. 5. Piping to be Securely Supported. Piping installed under ceilings shall be securely supported by substantial metal hangers, so spaced that there will be no sag in piping between points of suspension, and where run on walls shall be securely supported by metal brackets or pipe supports similarly spaced. Supports shall be so arranged that there will be no undue strain on the threads of any pipe or fittings. 6. Drips. All points at which accumulations of water or condensation are liable to occur in steam supply pipes shall be properly dripped, the method of such dripping to be subject to the approval of the Building Inspection Division of the Department of Planning and Community and Economic Development. No steam main shall be dripped into a dry return which carries radiator or unit heater condensate without either sealing or trapping such drip. The seal shall be of adequate depth to compensate for pressures involved. 7. Radiator and Boiler Connections. Supply and return connections to radiators and boilers shall be in accordance with the following provisions. 8. Radiator Connection. In two-pipe steam systems, the return connection for each radiator shall be made at the bottom of the radiator by means of either an eccentric bushing turned down or a water-leg section and the supply connection shall be made at the opposite end of the radiator either at top or bottom. 9. Boiler Connections. Steam boiler outlets shall not be bushed. Steam boilers with multiple outlets shall have at least two (2) of these outlets connected to a header the area of which shall be at least equal to the combined areas of the steam supply mains connected to it. All steam boilers used in connection with systems having gravity returns shall be provided with a Hartford return connection. Equalizer shall be taken from the bottom of the horizontal header. No return lines shall be connected together above the waterline of the boiler. Note. Steam boilers with multiple outlets may use one (1) outlet if the area of the outlet is equal to or greater than the steam main and is recommended by the boiler manufacturer. (b) Condensation Pumps, Vacuum Pumps, Boiler Feed Pumps and Combination Thereof, Etc. Capacity and Installation Requirements. The following provisions shall govern the capacities and manner of installation of all condensation pumps, vacuum pumps, boiler feed pumps and combinations thereof, traps, etc. hereafter installed in connection with steam heating plants. Capacities. In all cases where condensation pumps or vacuum pumps or boiler feed water pumps, or any combination of such devices, or traps, etc., are used in connection with steam heating plants, the capacity of each such device or combination of devices shall be subject to the approval of the Building Inspection Division of the Department of Planning and Community and Economic Development. Pipe connections shall be independently supported in such manner as to prevent undue stresses in pumps or traps, due either to weight or expansion. All equipment shall be installed in accordance with the manufacturer's recommendations, subject to the approval of the Building Inspection Division of the Department of Planning and Community and Economic Development. (c) Sizes of Mains, Risers and Radiator Connections for Hot Water Systems. 1. Sizes of mains, risers, and radiator connections shall be selected from capacity tables as shown in the American Society of Refrigeration and Air Conditioning Engineers' Guide as listed in Appendix No. 1. Piping systems shall include an expansion tank of proper size. 2. Forced Hot Water System. Sizes of mains, risers and radiator connections shall be selected according to the method and data given in the American Society of Refrigeration and Air Conditioning Engineers' Guide as listed in Appendix No. 1. The amount of water required in gallons per minute shall be determined by the following formula: G.P.M. equals Total BTU per hour divided by the Temperature drop times sixty (60) times eight (8). Where sixty (60) equals Minutes Per Hour and eight (8) equals Pounds Per Gallon of Water. A maximum temperature drop of twenty (20) degrees shall be used in determining G.P.M. requirements for forced hot water system. 3. Selection of Pumps. Pumps shall be selected from manufacturer's pump capacity charts. The minimum allowable head pressure shall be two and one-half (2½) feet. 4. Size of Pipe to be Installed. Having determined the equivalent length of pipe in the longest circuit and the total gallons per minute for the entire system, the sizes of pipe to be used for mains and risers shall be selected from the American Society of Refrigeration and Air Conditioning Engineers' Guide, as listed in Appendix No. 1. The friction loss per foot of pipe shall be between one hundred (100) and five hundred (500) mil-inches. (7) Piping and Piping Connections and Equipment for Hot Water Heating Systems. Piping and piping connections and equipment hereafter installed for all hot water heating plant installations or portions of such installation, shall conform to the following requirements: (a) Pipe, reaming, fittings and joints, expansion and contraction and piping supports for hot water heating systems shall conform to Section 30.13(4)(a)1, 2, 3, 4, and 5. (b) Pitch. All piping shall be pitched either up or down so that all gases which are liberated from the water can move freely to a vented section of the system. Whenever practicable, the pipe line shall be the same direction as the water when a pipe system cannot be installed without creating air pockets, that is, sections in the system from which liberated gases cannot escape, such sections shall be provided with air relief valves which may be operated manually when necessary. (c) Drainage. All piping shall be arranged so that the entire system can be drained, either to permit alterations or repairs, or to prevent freezing if the system is not to be operated during a cold period. (d) Friction Head to be Equalized. The piping system shall be installed so that each circuit has its correct friction head. This shall be accomplished by making the pipe line as short as possible and providing as few fittings as possible where it is necessary to minimize the friction, and by increasing the length of pipe and number of fittings where necessary to increase the friction. Where the correct balance cannot be obtained by use of pipe and fittings, balancing cocks or orifices shall be used. Whenever two (2) or more heating circuits are connected to the same source of supply, balancing cocks shall be installed in each branch circuit. (e) Expansion Tanks and Relief Valves. Expansion tanks and relief valves shall be installed in accordance with the following provisions: 1. Expansion Tanks for Open Systems. Each open hot water system shall be provided with an expansion tank which meets the following minimum requirements: The minimum contents of an open tank should be six-hundredths (.06) of the volume of the water in the system, including that in the boiler, heat transmitters, pipes, etc. They shall be located at least three (3) feet above the highest radiator. Provisions must be made to prevent freezing of the water in the tank as well as in the pipe leading to the tank. In gravity circulation systems, the pipe to the open expansion tank shall be connected to the supply riser from the boiler, so that air liberated from water in the boiler will enter the expansion tank. In forced circulation systems, the pipe of an open expansion tank should be connected on the suction side of the circulating pump. 2. Closed Expansion Tanks. Minimum contents of a closed expansion tank must be such that, the expansion of the water due to the increase in temperature, will be cushioned against a reservoir of compressed air above the water level in the expansion tank. Manufacturers' ratings of expansion tanks, or method for selecting expansion tanks as given in Section V of Bell & Gosset Co. Engineering Manual—1954 Edition, may be used in selecting the expansion tank. 3. Relief Valves. All boilers shall have an A.S.M.E. approved pressure relief valve rated at the full gross rating of the boiler output. There shall be no valves between the boiler and the relief valve. The discharge from the relief valve and the discharge from the low water cutoff shall be piped full size to within eighteen (18) inches of the floor. When water feed valves are used, a minimum size of one-half (½) inch shall be used and a valved bypass shall be installed. Valves shall be installed upstream and downstream from the feed valve. (8) Minimum Requirements for the Design and Installation of Hot Water and Radiant Panel Heating Systems. (a) Hot Water Radiant Panel Heating System. All hot water radiant panel heating systems shall be designed according to standards set forth in American Society of Refrigeration and Air Conditioning Engineers' Guide or Part VI, Panel Heating Contractors - National Association Mechanical Contractors Association of America as listed in Appendix No. 1. (b) Panel Surface Temperature. The maximum surface temperature for floor panels shall be eighty-five (85) degrees and for ceiling panels one hundred twenty (120) degrees. Screw threads will not be permitted in coils or grids embedded in concrete slabs or in plaster. Ferrous fabrication shall be all welded except in equipment room above floor or in boxes or covered recesses in slabs where flow adjusting cocks are installed. (c) Piping or Tubing Located in Concrete Slabs. Where nonferrous pipe or tubing is used in concrete slabs or in plaster, solder sweat fittings shall be used throughout and no ferrous to nonferrous connections shall be embedded in concrete, in plaster or concealed in the construction, nor shall nonferrous pipe or tubing come in contact with steel reinforcing in slabs. Threaded pipe and fittings may be used in equipment room above floor or in accessible recess boxes where adjusting flow cocks are installed in slabs. A balancing cock or valve shall be installed in each individual coil branch, either on the supply side or on the return side. (9) Requirements for Concealed Piping for Hot Water and Steam Systems. Concealed or embedded pipe or tubing shall be tested before being covered to a hydrostatic or compressed air pressure of not less than one hundred (100) pounds gauge for a period of not less than four (4) hours.
(Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (Am. by Ord. 8081, 7-29-83; ORD-08-00109, 10-7-08) (R. & Recr. by Ord. 4438, 1-7-74)
Ask a question about Madison law
Corpus searches the Madison sections it holds and shows the ones that match, with their citations. Free, no sign-in.