30.07 - GAS-FIRED UNIT HEATERS.
(1) Support. Suspended type gas-fired heaters shall be safely and adequately supported with due consideration given to their weight and vibration characteristics. (2) Clearances. Listed gas-fired heaters shall be installed with minimum clearances of six (6) inches between the appliance, projecting flue box or draft hood and combustible construction. The control side of a unit heater shall be spaced not less than eighteen (18) inches from any wall or partition. Unlisted unit heaters shall be installed with clearances to combustible construction of not less than eighteen (18) inches, or in accordance with Section 30.06(4)(f)2. of the Madison General Ordinances. Combustible floors under unlisted floor mounted heaters shall be protected in an approved manner. (3) Negative Pressure. The location of any unit heater or the ductwork attached thereto, shall be such that a negative pressure will not be created in the room in which the unit heater is located. (4) Ductwork. A unit heater shall not be attached to a warm air duct system unless listed for such installation.