Omaha Municipal Code § 49-1120 Exterior grease interceptors.
Sec. 49-1120. - Exterior grease interceptors.
(a) General:
(1) Concrete interceptors, not certified to ASME A1 12.14.3 (Type C) standards, shall hereafter be referred to as "non-certified interceptors."
(2) Interceptors constructed of fiberglass reinforced polyester and high density polyethylene, which are certified to ASME A1 12.14.3 (Type C) standard and approved by the plumbing board as to design and material, shall hereafter be referred to as "certified interceptors." The plumbing board shall keep a list of all approved products on file with the plumbing board secretary.
(b) In addition to subsection (a) above all interceptors shall conform to the following:
(1) Shall be designed to withstand anticipated loads for both earth and traffic loads and constructed of the materials as referenced in section 49-1123.
(2) Waste other than kitchen waste shall not be connected to a grease interceptor with the exception of a hand sink.
(3) The effluent from the grease interceptor shall connect to the building sewer or the inlet of the septic tank.
(4) Where the building sewer is not accessible the discharge may reenter the building and connect to the building drain when approved by the chief plumbing inspector.
(5) The piping from the building to the outlet of the interceptor shall be considered as part of the building drain and, if the discharge piping from the interceptor reenters the building, all of the piping shall be considered to be part of the building drain system.
(6) Each chamber shall have a minimum of 24-inch diameter access located over the inlet and outlet with a minimum clear opening of 22 inches.
(7) The covers shall be bolted air tight and securely attached to the top of the tank and designed to withstand traffic loads.
(8) A two-way cleanout shall be provided at the inlet and outlet sides of the interceptor, however the outlet two-way cleanout will not be required if an inspection manhole is required.
(9) Interceptors shall be required to be filled with water as follows:
(a) Two piece non-certified and all certified interceptors shall be filled with water to the level of the outlet before backfilling.
(b) All certified interceptors shall be filled with water to the level of the outlet before backfilling.
Exemption: One piece non-certified interceptors shall not be required to be filled with water.
(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 36, 8-13-21)