1103.5.4. [For SF] Automatic Sprinkler System for Existing High-Rise Buildings.
All existing residential high-rise buildings shall be equipped with an automatic sprinkler system in accordance with Section 903.3.1.1 where any of the following conditions apply:
1. The high-rise building has an occupied floor located more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access.
2. The high-rise building has occupied floors located more than 75 feet (22 860 mm) and not more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access, and the building does not have at least two interior exit stairways complying with Section 1104.10 that are separated from the building interior by fire assemblies having a fire resistance rating of not less than 2 hours with opening protection in accordance with Table 716.1(2) of the California Building Code.
3. The high-rise building has occupied floors located more than 75 feet (22 860 mm) and not more than 120 feet (36 576 mm) above the lowest level of fire department vehicle access, and the building does not have a fire alarm system that includes smoke detection in mechanical equipment, electrical, transformer, telephone equipment and similar rooms; corridors; elevator lobbies; and at doors penetrating interior exit stairway enclosures.
Existing high-rise buildings that are also qualified historical buildings as defined in California Health and Safety Code Section 18950 shall be provided with an approved automatic fire sprinkler system when and as required by the State Historical Building Code.
Exceptions:
1. Apartment houses, condominiums, or other Residential Group R-2 Occupancies (classified as R-1 prior to 2008), until January 1, 2035, when this exception expires.
2. A mixed-use occupancy building containing a Residential Group R-2 Occupancy (classified as R-1 prior to 2008), until January 1, 2035, when this exception expires.
Any existing high-rise not exempted from this section that does not provide an automatic sprinkler system throughout the residential occupancy is out of compliance and subject to immediate code enforcement action. The owner shall maintain the sprinkler system in accordance with Title 19 of the California Code of Regulations.