Interceptor requirements.
Riverside Municipal Code § 14.12.260
in effect14.12.260 - Interceptor requirements.
A. The interceptor shall be watertight, structurally sound, durable, and shall have a minimum of two chambers, excluding sample box, with a separate ring and cover for each chamber. The sample box shall also have a separate ring and cover. All rings shall be affixed to the interceptor to ensure a gas and watertight seal.
B. Each grease interceptor cover shall expose and provide access to each chamber's inlet tee, outlet tee, and/or mid-wall tee.
C. All interceptor chambers shall be immediately accessible at all times for inspection, sampling, cleaning, and maintenance. The user shall provide a separate ring and cover for each separate interceptor chamber, including sample box and any additional covers to ensure adequate cleaning and inspection capabilities. All rings shall be affixed to the interceptor to ensure a gas and watertight seal. At no time shall any material, debris, obstacles or other obstructions be placed in such a manner that will prevent immediate access to the interceptor.
D. Any interceptor legally and properly installed before the effective date of this chapter shall be acceptable as an alternative to the interceptor requirements of this chapter providing that the interceptor shall be effective in removing floatable and settleable material and shall be immediately accessible for inspection, sampling, cleaning, and maintenance.
E. All drains and openings connected to an approved gravity separation grease interceptor shall be equipped with screens or devices which will exclude from the wastewater discharge all material and particles greater than three-eighths of an inch in any dimension.
F. All gravity separation grease interceptors shall be equipped with an influent tee extending no more than six inches below the operating fluid level of the interceptor. The interceptor shall also have tees extending to within 12 inches of the bottom at the exit side of each chamber in the interceptor, including the final chamber. In a case where a manufacturer's engineered interceptor design is contrary to this requirement, the Director shall review the design and either approve or deny an exemption to this requirement.
G. All interceptors shall be equipped with a sample box or sample wye as determined by the Director.
H. No user shall install or use any elbows or tees in any interceptor sample box.
I. No user shall install any interceptor, sample box, or sample wye in a confined space or a permit-required confined space.
J. At all times, all drain lines connecting to the interceptor shall be kept free of any debris or material that may cause a drain line blockage and periodically cleaned or maintained as needed.
K. If the Director finds, either by engineering knowledge or by observation, that an interceptor is incapable of adequately retaining floatable and settleable material in the wastewater flow, is structurally inadequate, or is undersized for the facility, the Director may reject such interceptor and declare that the interceptor does not meet the requirements of this section. The user shall thereupon be required to, modify or repair the interceptor, or install an adequate interceptor, acceptable to the Director at the user's expense.
(Ord. 7551 §10, 2021; Ord. 7362 §6, 2017; Ord. 7032 §2, 2009; Ord. 6637 §2 (part), 2002; Ord. 6232 §2 (part), 1995)
Source: City of Riverside, California, Municipal Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/ca/riverside/codes/code_of_ordinances?nodeId=PTIICOOR_TIT14PUUT_CH14.12DIWAINPUSEPOINSTDRSY_DIVIIGEPR_14.12.260INREFetched: 11/1/2026