SEC. 11-715. - ADDITIONAL SMOKE CONTROL REQUIREMENTS.
Existing air conditioning and ventilation systems may be used as part of the smoke-control system. Existing return air plenum and approved fiberglass air ducts may be used as part of the smoke-control system. A smoke exhaust system shall be designed in a manner that will prevent smoke from going from one room to another, except when two or more rooms are connected together by means of a permanent unobstructed opening at least 20 square feet with a minimum three feet dimension, then the rooms shall be considered as one room for the purpose of designing the smoke-control system.
(Added Ord. 2007-102, § 1, eff. 1-20-08).