§ 94.31. - Fire protection systems, components, installation, and maintenance requirements.
(a) All fire alarm detection systems shall be installed in accordance with the requirements of the NFPA Fire Code Standard 72, 2019 edition. Where documentation is required by the authority having jurisdiction, the following list shall represent the minimum documentation required for new systems and additions or alterations to existing systems:
(1) Written narrative providing intent and system description.
(2) Riser diagram.
(3) Floor plan layout showing locations of all devices, control equipment, and supervising station and shared communications equipment with each sheet showing the following:
a. Point of compass (north arrow).
b. A graphic representation of the scale used.
c. Room use identification.
d. Building features that will affect the placement of initiating devices and notification appliances.
(4) Sequence of operation in either an input/output matrix or narrative form.
(5) Equipment technical data sheets.
(6) Manufacturers' published instructions, including operation and maintenance instructions.
(7) Battery capacity and safety margin calculations (where batteries are provided).
(8) Voltage drop calculations for notification appliance circuits.
(9) Mounting height elevation for wall-mounted devices and appliances.
(10) Where occupant notification is required, minimum sound pressure levels that must be produced by the audible notification appliances in applicable covered areas.
(11) Locations of alarm notification appliances, including candela ratings for visual alarm notification appliances.
(12) Pathway diagrams between the control unit and shared communications equipment within the protected premises.
(13) Completed record of completion in accordance with [sections] 7.5.6 and 7.8.2.
(14) For software-based systems, a copy of site-specific software, including specific instructions on how to obtain the means of system and software access (password).
(15) Record (as-built) drawings.
(16) Records, record retention, and record maintenance in accordance with section 7.7.
(17) Completed record of inspection and testing in accordance with [sections] 7.6.6 and 7.8.2.
(b) All fire suppression systems and components shall be installed in accordance with the requirements of NFPA Installation of Sprinkler Systems Standards 13, 13R, and 13D, 2002 edition.
(c) All special engineered fire protection systems shall comply with referenced NFPA standards, in their entirety, listed in chapter 80 of the 2018 International Fire Code.
(d) All cooking hood suppression systems in use within the jurisdiction of the City of Springfield must meet the requirements of NFPA 17A Wet Chemical Extinguishing Systems and Underwriters Laboratories 300.
(e) All fire alarm detection systems connected to a light and power service shall be on a dedicated branch service. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to personnel authorized by the owner of the system and shall be clearly marked "fire alarms circuit control" as required by the NFPA Fire Code Standard 72, 2019 edition.
(f) Fire protection systems that are required to have monitoring of the signal shall meet the requirements of NFPA 72, 2019 edition for monitoring and all components thereof.
(g) All fire protection systems, required or non-required by any code, shall be installed, maintained, and operated per manufacturer recommendations, and pursuant to adopted codes and regulations governing those fire protection systems. Fire protection systems shall not generate false alarms due to a preventable system defect, lack of maintenance, employee error, or malfunction.
(h) No fire alarm detection device(s) may be installed or allowed to be a part of a zone, loop, or other similar devices, of a security system unless the security system is of a listed and approved type capable of operating the fire detection device(s). The security device shall be capable of providing a means to identify the difference between a fire detection signal, and a security system activation when reporting a signal to a remote monitoring site.
(i) Fire alarm and fire suppression companies which provide maintenance, servicing, and/or monitoring services to occupancies within the jurisdiction of the City of Springfield must notify the fire safety division in writing, seven days prior to removal of any component or service of any existing system. Similar notification shall be provided within 24 hours of an emergency situation that decreases the life safety protection of an occupancy within the jurisdiction of the City of Springfield.
(j) Electronic supervision of fire suppression control valves is required. Chain and padlock type security is not allowed.
(k) Rooms containing fire extinguishing system controls and communications equipment shall be identified in an approved manner.
(l) Owners of occupancies must at all times provide a local representative who has the responsibility and authority to respond to and assist emergency personnel during response to an occupancy. The owner of the occupancy shall ensure that said representative will be onsite within one hour of notification of the owner, property representative, or an authorized answering service.
(m) Owners of occupancies protected by a fire alarm system with or without monitoring of signals must provide information regarding the means by which the local representative responsible in subsection (l) above may be contacted. This information may be either posted on site where the alarm is installed, or provided to the alarm company responsible for servicing the system. Any changes to contact information must be updated within five days of the change.
(n) A record of all periodic inspections, tests, servicing and other operations and maintenance shall be on the premises for a minimum of three years and shall be made available upon request to the fire code official on request. Additionally, current inspection and testing records shall be submitted to the fire safety division or its designee within 14 business days.
(o) Deficiencies noted on fire protection systems inspections, testing and maintenance shall be abated and a subsequent inspection noting all corrections and deficiencies abated shall be submitted.
(Ord. No. 190-04-06, § 1(Exh. A), 4-4-06; Ord. No. 489-07-07, § 1(Exh. A, 7-17-07; Ord. No. 056-02-23, § 1(Exh. A), 2-21-23)