30-0305. - Gas burner installation.
A-1. No apparatus or equipment to be used with gas supplied from the general gas distribution system of Xcel Energy within the city shall be installed or connected for use without a permit having been secured therefor from the building inspector.
A-2. Repealed by Ord. No. 2568 (1991).
A-3. Xcel Energy shall refuse gas service to the premises wherein any gas-fired installation or connection is made contrary to the terms of this chapter, upon discovery of same, until the same has been remedied or disconnected and removed.
A-4. All installations of mains, regulator stations, services, and meter installations shall conform to the gas construction standards on file in the office of the city engineer. Such standards shall not be effective until approved by the board of city commissioners and any changes in such standards shall not be effective unless approved by the building inspector. However, regardless of such standards, every high or medium pressure service shall have an outside shutoff valve and all low pressure services installed after January 1, 1962, shall have outside shutoff valves.
B-1. Scope. The construction arrangement, manner of installation, alteration and repair of all gas burners, gas-burner equipment and appliances as herein defined having an input capacity of 400,000 BTU per hour or less shall conform to provisions of this chapter.
B-2. Definitions. For the purpose of this section the following definitions shall apply:
A. Gas burners and gas-burner equipment. The term "gas burner" shall mean a device for the final conveyance of gas or a mixture of gas and air to the combustion zone of a steam or hot-water boiler, furnace, or any device or appliance used in connection with a space-heating system, and shall include conversion burners, gas-designed heating appliances, power gas burners and atmospheric gas burners. The term "gas-burner equipment" shall include gas burners as above defined, together with all fans, blowers, control devices, accessories connected to the burners, and piping involved in supplying the burner.
B. Conversion burner. The term "conversion burner" shall mean a gas-burning device designed to supply gaseous fuel to and properly burn this fuel in the combustion space of equipment, originally designed to burn another fuel.
C. Gas-designed heating appliance. The term "gas-designed heating appliance" shall mean any space-heating appliance designed for the exclusive use of gaseous fuel, excepting such auxiliary heaters as gas logs, radiant heaters, etc.
D. Power Gas Burner. A "power gas burner" is one in which either gas or air or both are supplied at pressures exceeding, for gas, the normal line pressure at the burner and for air, atmospheric pressure, the added pressure being applied at the burner.
E. Atmospheric burner. An "atmospheric burner" is a device (other than a gas range or a gas water heater) in which air at atmospheric pressure is injected into the burner by a jet of gas under pressure not more than the house line pressure and whose input exceeds 50,000 BTU per hour.
B-3. Approval of gas burners. It shall be unlawful for any person, firm, corporation, or agent to install any gas burner, as defined within this chapter, until such gas burner has been approved by the building inspector. The building inspector may approve all gas burners meeting the minimum requirements for approval or listing by the American Standards Association, sponsored by the American Gas Association, or other nationally recognized testing laboratory and in compliance with requirements of this chapter.
B-4. Installation of used gas burners. It shall be unlawful to install any used gas burner, and no permit shall be issued authorizing such installation, until the licensed installer shall have first submitted with his application for permit a copy of the purchase order stating that a used burner is to be installed and bearing an acknowledgment by the purchaser that such is the case together with a statement by the licensed installer that said burner has been reconditioned and will comply in every way with ordinance requirements for new equipment as to operation, safety standards, and adjustments. No used gas burner shall be installed unless it is of a type, make, and model currently approved for installation in the city.
B-5. Type of gas. The requirements of this chapter shall apply to gas burners supplied with natural gas from the general distribution system within the city. Burners and their installation where supplied with other types of gas, such as bottled or liquefied petroleum gas, shall conform to the requirements of this chapter where applicable together with the requirements of the American Gas Association and the National Board of Fire Underwriters pertaining to the type of gas to be used.
B-6. Ventilation. Gas burners and gas-burning appliances as hereinbefore defined shall not be installed for operation in a room where the normal facilities for ventilation do not permit proper combustion of the gas, unless special provision is made for supplying sufficient air for complete combustion.
Gas burners, gas-burner appliances and space heaters will not be permitted in bedrooms, rooms used for sleeping purposes, bathrooms, or any confined space or area unless proper provisions are made for the supply of primary and secondary air for combustion from outside the building. Provisions shall also be made for proper venting to the outside.
Regulations for the method of securing air for combustion and the proper venting of the appliances shall be secured from the building inspector before work is started on any specific installation.
B-7. General. The installation of conversion burners shall be made in conformance with the American Standards Association requirements as sponsored by the American Gas Association and with requirements herein set forth.
B-8. Preparation of boilers and furnaces. Before a gas burner is installed in any existing boiler or furnace, all flues, fire pots, combustion chambers, and connecting joints through which flue gases are conducted shall be thoroughly cleaned, examined for leaks and draft conditions, and made gas-tight as shown by a smoke-bomb test or its equivalent.
B-9. Flues and flue pipes. The chimney flue and flue pipe shall be examined and reconditioned if necessary so that they will freely conduct the flue gases to the outer air. Where flue pipes are rusted or burned out, they shall be replaced by new pipe.
B-10. Removal of oil burners. Where a gas burner is installed and an oil burner removed, it shall be mandatory that the vent and fill pipes to the storage tank be removed and all openings to the storage tank plugged.
B-11. Draft hoods. Each gas-burning appliance shall be equipped with a draft hood or its equivalent designed to:
A. Insure the ready escape of the products of combustion in the event of no draft, back draft, or stoppage beyond the appliance.
B. Prevent a back draft from entering the appliance.
C. Neutralize the effect of stack action of the flue upon the operation of the appliance.
The draft hood shall be placed in and made a part of the flue pipe from the appliance or shall be in the appliance itself. Such device shall have a free area equal to or greater than the cross-sectional area of the flue pipe connected thereto subject to the approval of the building inspector.
The draft hood shall be located at a point not lower than the top of the highest flue passage in the appliance.
Appliances of the revertible flue type shall have the draft hood located at least one foot higher than the top of the highest flue passage. Proper provision shall be made, subject to the approval of the building inspector, to prevent the accumulation of gas in any part thereof. Revertible flue-type furnaces shall have as a minimum a two-inch bleeder cut through if trapped more than 12 inches.
B-12. Flue pipes. The internal cross-sectional area of the flue pipe between the appliance and the chimney liner shall be such as to provide not less than one square inch of flue area per 7,500 hourly BTU input. In no case shall this flue pipe be less than five inches in diameter for central-heating gas appliances nor less than four inches in diameter for space-heating appliances and it shall not be larger than the next integral inch diameter above the sizes given in the following table:
MINIMUM PERMISSIBLE FLUE SIZES
FOR GAS BURNER INSTALLATIONS*
Input Rating BTU per hour | Area of Flue Outlet—Sq. inch. | Diameter Flue Pipe—Inches
95,500 | 12.6 | 4
147,000 | 19.6 | 5
212,250 | 28.3 | 6
288,750 | 38.5 | 7
377,250 | 50.3 | 8
477,000 | 63.6 | 9
Based on 1 square inch flue area per 7,500 BTU per hour input.
*NOTE: If flue pipe exceeds 10 feet in length or contains more than two elbows, use next size larger pipe and draft hood.
In cases where the outlet from the appliance is larger than the above-indicated size, an orifice plate may be inserted, or a section of the flue pipe restricted to the size indicated between the appliance outlet and the draft diverter. In special cases with high chimneys or flues, the above schedule of areas may be modified subject to specific approval of the building inspector.
The draft hood should ordinarily be located adjacent to the appliance. In cases where it appears desirable to place the draft hood at a distance from the appliance, the size of the restricted section may be modified according to the length and rise of the flue pipe.
The proportioned section at the flue outlet of the appliance eliminates the necessity of using an adjustable damper in the flue pipe and such damper will not be permitted.
Where dampers are an integral part of the boiler or furnace, they shall be removed or permanently secured in the wide-open position, except such dampers the function of which is to alter the passage of the flue gases through the appliance, which shall be locked in such a position as not to interfere with the normal operation of the burners.
B-13. Material used for flue pipe shall be such as to resist the corrosive action of flue gases.
Flue pipe of existing systems shall be relocated where necessary and new flue pipe installations shall be so made as to avoid sharp turns or other constructional features which could create excessive resistance to the flow of flue gases. Flue pipe shall slope upward to chimney.
Flue pipe shall be tightly connected to the chimney liner, so as to prevent infiltration of cold air.
No baffles shall be applied which will interfere with the proper combustion of gas.
Flue pipe shall be well supported to prevent sagging and shall not be installed closer than six inches to any combustible building materials unless flue pipe is covered with incombustible insulation such as will permit the surface temperature of the exterior surface thereof to attain a temperature of not higher than 125° Fahrenheit when the appliance is under continuous operation.
All space-heating equipment shall be of the vented type and properly vented to an effective flue. Heaters of a sealed-unit type vented through a wall to the atmosphere will be accepted if approved by the American Gas Association.
B-14. Radiant heaters or other unvented heaters may be installed in fireplaces providing the chimney has a positive draft with the damper closed.
B-15. Gas burners. Gas burners of all types shall consist of assembled and tested units and shall be accompanied by complete and comprehensive installation and operation instructions. The burner or burners shall be located according to the manufacturers' instruction and shall be so secured that they will not twist, slide, or drop out of position.
B-16. The burners shall be so installed as to be readily accessible for cleaning and inspection. The burner or burners shall be so installed that no part of the flames impinge on the heating surface so as to cause incomplete combustion. Air shutters shall be adjusted to produce a proper flame at the prevailing gas pressure.
On all installations where the combustion air pressure can exceed the house line pressure, an approved check valve or other approved device shall be installed in the gas supply line to prevent air from backing into the gas line.
B-17. Air intake. Where secondary air is necessary, secondary air opening or openings shall be provided of sufficient area to supply an adequate amount of air for complete combustion under the specified draft conditions and at the maximum rate of firing.
Where an automatic secondary air control is provided, the construction shall be such that, in case the control fails in any way, either the gas will be shut off or the secondary air door will remain open.
The air intake of power burners shall be so located as to prevent the possibility of accidental closure. The gas and air supply shall be equipped with controls coordinated to prevent opening of the gas supply until the air supply is adequate for proper combustion and to shut off the gas supply in the event of failure of the air supply.
B-18. Pilots. Each gas burner shall be equipped with a safety device arranged to prevent the flow of gas through the main burner unless the pilot flame is burning. The device shall consist of a thermostatic pilot or other approved type of safety device. The operation of this device shall not depend upon the closing of an electric circuit to shut off the main gas supply. Gas burners installed under subsection B-14 are exempt from this provision.
Pilot burners shall be rigidly supported in such a manner that their position relative to the main burner or burners will be fixed.
Pilot burner or burners shall be so placed that they can be safely lighted and they shall be readily accessible or removable for cleaning.
The gas supply line to the pilot or pilots shall be connected to vertical main gas supply lines or to the side or top of horizontal lines ahead of the main burner governor and appliance shutoff valve and shall be provided with a separate cock. Provided, however, that where complete shutoff-type automatic pilot is provided with approved flow interrupter, the pilot line shall be connected to this control and such control shall be located ahead of the main burner governor and after the appliance shutoff valve.
Room heaters, floor furnaces and recessed wall heaters shall be equipped with complete shutoff type of automatic pilot.
Thermostatic safety pilots shall be so adjusted that under continuous operating conditions the main gas supply will be shut off within three minutes after pilot flame has been extinguished.
Copper or iron tubing shall not be used for supply piping within the burner heat zone to pilot burners.
B-19. Main shutoff valve or cock. A manually operated, approved shutoff valve or cock shall be installed at each appliance to shut off the entire gas supply to appliance.
Such valve or cock shall be so located that it is readily accessible at about five feet above the floor, and shall clearly indicate the "on" and "off" positions, or direction of rotation to open or close. Where a cock is provided, the opening handle shall be securely attached to the plug in such manner that it may not be readily removed.
B-20. Automatic control. Electric control valves shall be installed according to the instructions furnished by the manufacturer. All heating equipment shall be automatically controlled by thermostat except heaters installed in fireplaces as provided in subsection B-14.
B-21. Electric wiring. All electrical connections shall be made in accordance with the provisions of all building and electrical codes relating to the installation of electric wiring in the city of Fargo.
B-22. Gas pressure regulators. An approved gas pressure regulator shall be installed on the downstream side of the pilot supply on all gas burners, and a pressure regulator and pilot filter shall be installed in all pilot lines, downstream from the pilot shutoff cock, on all burners. Pressure regulators and pilot filters shall be of a type listed for approval by the American Gas Association and shall be approved by the building inspector.
B-23. Limiting devices. The boiler or furnace shall be equipped with safety devices arranged to limit high steam pressures or water temperatures, as well as high air temperature in warm-air furnaces, and all such devices shall be subject to the approval of the building inspector.
Each gas-fired steam boiler shall be equipped with a low-water cutoff approved by the building inspector.
Safety devices operated electrically shall not depend upon the closing of a circuit to shut off the main gas supply. This requirement shall not be construed as prohibiting the use of electrical regulating devices, providing the required safety devices are also installed. Controls shall be so connected that maximum inherent safety provided by such controls will be attained.
Safety shutoff valves, if used, shall be tested to assure gas-tightness of the seat when in the closed position; the valve assembly shall be gas-tight in all positions. Packing glands shall be designed so that the valve will not be made inoperative by excessive tightening of the packing nut.
Either the valve shall incorporate means for requiring a manual operation for reopening of the valve after it has closed or the electrical circuit shall be so arranged as to require a manual operation to reopen the valve after it has been closed. In no case shall valves be able to be opened manually until safety pilots are lighted and circuit completed or low-water cutoff circuit has been completed.
B-24. Piping. Gas piping installed for serving conversion burners or gas-designed heater appliances shall be sized for a total pressure drop not exceeding 0.5 inches water gauge from the meter to the burner for the total connected load. A separate pipe from the meter is to be preferred and in no case shall the service pipe be smaller than the size of equipment connection. All gas piping shall be installed in conformance with the provisions of this chapter and in conformance with American Standard Association's requirements.
Subsection B-25 is deleted in its entirety and the remaining subsections of section 30-0305 shall be renumbered accordingly.
* * *
B-28. Burner operation. . . .
NOTE: In making the test under subsection B-28, care shall be exercised to prevent the accumulation of unburned gas in the appliance or flues which might result in explosion or fire.
* * *
B-30. Instructions to the owner and/or occupant. The owner and/or occupant shall be thoroughly instructed by the installer as to the proper and safe operation of the appliance before it is placed in service, such instructions to include actual demonstration to the customer or his authorized agent of the processes of lighting and turning off the gas burner. A printed set of instructions enclosed in an envelope labeled "Instructions to Customer" shall be securely attached to the gas valve.
* * *
C-10. Venting of controls. Pressure regulators, slow-opening gas valves, and other gas equipment requiring venting shall be vented to a safe point outside of the building.
* * *
C-13. Inspection and tests. All installations shall be carefully tested for the proper operation of all controls and electrical circuits.
Piping shall be carefully tested for leaks.
* * *
Source: 1952 Rev. Ord. 968 (1956), 1087 (1960), 2467 (1989), 2796 (1996), 4599 (2007).