§ 11-712 — SMOKE DAMPERS

Fresno Municipal Code (Supp. No. 55, Update 1 (online June 23, 2026): codified through Ordinance No. 2026-019) · Fresno Municipal Code § 11-712

Corpus is an independent public-information project, not the official City of Fresno website. Stable reference: corpuslaw.us/code/ed7c1bd8-b00d-4b77-8eb5-8f4c5254e56a

SEC. 11-712. - SMOKE DAMPERS.

If a smoke-control system serves more than one floor, then smoke dampers shall (i) be installed in the main exhaust air ducts and the main supply air ducts serving each floor and (ii) comply with the activation requirements of C.B.C. Section 713.10.2. The smoke dampers shall be installed in a manner that will prevent the movement of smoke from one floor to another floor when the dampers are closed. The vertical risers of the main exhaust air duct shall be installed in metal ducts complying with the requirements for product-conveying ducts in Chapter 5 and 6 of the Mechanical Code. In the firefighter's control panel, all smoke dampers within the same smoke-control zone shall be actuated by one On-Auto-Off switch in accordance with C.B.C. Section 905.13.2, except that an alternate actuation method may be allowed when approved by both the Fire Department and the Department. Combination fire and smoke dampers, and smoke dampers shall be listed to conform to UL 555 and they shall be accessible for inspection, service and repair. Pneumatic tubing to operate these dampers shall be of noncombustible materials.

(Added Ord. 2007-102, § 1, eff. 1-20-08).

Ask a question about Fresno law

Corpus searches the Fresno sections it holds and shows the ones that match, with their citations. Free, no sign-in.