SEC. 11-713. - FIREFIGHTER'S CONTROL PANEL.
The firefighter's control panel shall comply with all the requirements of C.B.C. Section 905.13, except that graphically depicted representation of the building may be omitted when accepted by the Fire Department. The firefighter's control panel shall monitor and be capable of overriding the Mechanical Test Panel. The Mechanical Test Panel is a separate control panel which provides controls and displays the status of the ventilation fans, dampers, and other smoke control devices as required by C.B.C. Section 905 and shall be located in the same room as the Firefighter's Control Panel.
(Added Ord. 2007-102, § 1, eff. 1-20-08).