Sec. 7-1-6. - International Fuel Gas Code amendments.
Delete section 401.5 of the IFGC, 2015 ed.; Replace with revised section as follows: 401.5 Identification. All piping 2-PSI and higher shall be marked at the beginning, all ends and not less than 5 feet intervals along the length, designating the gas pressure. For low pressure piping, other than black steel pipe, exposed piping shall be identified by yellow label marked "GAS" in black letters. The marking shall be spaced at intervals not exceeding 5 feet (1524 mm).
(Ord. No. 10-112, 8-24-2010; Ord. No. 15-164 , 11-30-2015)