§ 33-104 — Installation of backflow prevention assemblies

The Code of the City of Tempe, Arizona (Supp. No. 34, Update 1: codified through Ordinance No. O2026.34, enacted June 25, 2026) · Tempe City Code § 33-104

Corpus is an independent public-information project, not the official City of Tempe website. Stable reference: corpuslaw.us/code/f567a8ae-60bc-4e17-a3f5-8fee8960f4e9

Sec. 33-104. - Installation of backflow prevention assemblies.

(a) Assemblies shall be installed at the service connection or near the property line but in all cases before the first branch line leading off of the service line, and in an accessible location approved by the department. (b) Backflow prevention assemblies shall have at least the same cross-sectional area as the water service and or meter. In those instances where a continuous water supply is necessary, two (2) sets of backflow prevention assemblies shall be installed in parallel, if the water supply cannot be temporarily interrupted for the testing of assemblies. (c) No bypass shall be installed around backflow prevention assemblies. (d) Double check valve assemblies shall be installed as prescribed in the standard details approved by the department. Copies of the standard details are available from the department. Double check valve assemblies may be installed below ground in a vault, if approved in writing, on a case-by-case basis by the department. (e) Reduced pressure principle assemblies shall be installed as prescribed in the standard details approved by the department. Copies of the standard details are available from the department. Reduced pressure principle assemblies shall be installed above ground. (f) All pressure-type backflow prevention assemblies, which are designed for periodic field testing, shall be equipped with resilient seated shut-off valves on both the upstream and the downstream side of the assembly. In addition, resilient seated test cocks shall be provided and located so that test equipment may be connected to the assembly at such points that the pressure in each pressure zone may be detected and, in addition, a test cock shall be located upstream of the upstream shut-off valve as close as possible to the upstream shut-off valve.

(Ord. No. 87.57, § 33-400, 1-28-88; Ord. No. 95.19, 7-20-95; Ord. No. 2004.15, 4-29-04)

Ask a question about Tempe law

Corpus searches the Tempe sections it holds and shows the ones that match, with their citations. Free, no sign-in.